Error messages
12.2
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EtherNet/IP: Class 3 Connection Closed [0x00c88143]
EtherNet/IP: Duplicate IP address [0x00c88273]
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
Scanner has closed a "Class 3" connection.
Check scanner functionality.
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
An IP address has been allocated twice within the
network. The addresses of the network nodes must differ
from each other.
Correct IP address (