12
Error messages
12.2
Possible causes and remedies
85
Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EtherNet/IP: Fault Mode [0x00c88111]
EtherNet/IP: Explicit Message Timeout [0x00c88112]
EtherNet/IP: Overall Ethernet communication timeout [0x00c88114]
EtherNet/IP: Idle Mode [0x00c88132]
EtherNet/IP: Class 1 Connection Closed [0x00c88142]
Response
(Lenze setting printed in bold)
Setting:
/
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Connection to scanner has been interrupted.
• Controlling I/O connection failed by timeout.
• Within the timeout time for implicit messages
parameterised by the scanner, no "implicit messages"
have been received.
• Check cables and terminals.
• Plug in the network cable into the Ethernet port.
• Check Requested Package Interval (RPI) of I/O
connection.
• Increase timeout time for implicit messages.
Response
(Lenze setting printed in bold)
Setting:
/
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Connection to scanner has been interrupted.
• Failure of an explicit connection
• Within the timeout time for explicit messages
parameterised by the scanner, no "explicit messages"
have been received.
• Check cables and terminals.
• Plug in the network cable into the Ethernet port.
• Check Requested Package Interval (RPI) of the explicit
connection.
• Increase timeout time for explicit messages.
Response
(Lenze setting printed in bold)
Setting:
/
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Failure of »Engineer« communication via Ethernet
• When the time set in
/
has expired,
there is no access via the »Engineer«.
• Check cables and terminals.
• Plug in the network cable into the Ethernet port.
• Increase the overall Ethernet timeout time in
.
Fault with regard to EtherNet/IP communication
Response
(Lenze setting printed in bold)
Setting:
/
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Scanner has received an idle event.
• The scanner is in the "PROG" mode.
• In the "Scanner Command Register", the Run/
Idle flag (bit 0) is 0.
Set the scanner to the run mode.
Run/Idle flag (bit 0) = 1
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
The scanner has closed the controlling "Class 1"
connection.
Check scanner functionality.