13
Parameter reference
13.3
Parameters of the communication module for slot MXI2
109
Lenze · E94AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 12/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14842
C14843
C14846
C14850
Parameter | Name:
C14842 | Supervisor IP Address
Data type: UNSIGNED_8
Index: 9733 = 0x2605
Display of the supervisor IP address
(Instance attribute 10 (Supervisor IP Address) in the
Device Level Ring (DLR) Object (71 / 0x47) (
Display range
(min. value | unit | max. value)
0
255
Subcodes
Info
C14842/1
Supervisor IP address (most significant byte)
C14842/2
Supervisor IP Address
C14842/3
Supervisor IP Address
C14842/4
Supervisor IP address (least significant byte)
Read access
Write access
CINH
PLC STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C14843 | Supervisor MAC ID
Data type: OCTET_STRING
Index: 9732 = 0x2604
Display of the supervisor MAC ID
(Instance attribute 10 (Supervisor MAC Address) in the
Device Level Ring (DLR) Object (71 / 0x47) (
Read access
Write access
CINH
PLC STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C14846 | Address Conflict Detection
Data type: UNSIGNED_8
Index: 9729 = 0x2601
Activation of the address conflict detection (ACD)
(Instance attribute 10 (Selectcd) in the
TCP/IP Interface Object (245 / 0xF5) (
)
Changing this value requires a reset of the device ("power off/on" or "type 0 reset").
Selection list
(Lenze setting printed in bold)
0 Deactivated
1 Enable
Read access
Write access
CINH
PLC STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C14850 | All words to scanner
Data type: INTEGER_16
Index: 9725 = 0x25FD
Display of the I/O data words transferred from the communication module (adapter) to the scanner.
In the subcodes, all I/O data words transferred to the scanner are displayed. However, only the configured I/O data
words are valid.
Display range
(min. value | unit | max. value)
-32768
32767
Subcodes
Info
C14850/1
...
C14850/32
Read access
Write access
CINH
PLC STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT