Configuration
Basic configuration
2−5
l
EDSVF9383V−EXT EN 2.0
Second digit
Defines the additional function. Extends the basic function.
Configuration of C0005
Additional function
x0xx
No additional function
x1xx
Brake control via digital output X5/A2
x2xx
Setpoint selection via motor potentiometer
x3xx
PID−controller for process data control
x4xx
Mains failure control
x5xx
Setpoint selection via digital frequency input
x6xx
Analog gearbox factor trimming
x7xx
Digital gearbox factor trimming
x8xx
Digital frequency ramp function generator
)
Note!
The most important codes for parameterising the basic configurations can be found
in the GLOBAL DRIVE CONTROL program and via the keypad under the "Short
setup" menu items.
Third digit
Defines if an internal or external voltage supply is to be used for the analog and digital control inputs.
Configuration of C0005
Supply voltage
xx0x
External
xx1x
Internal via terminal X5/A1 and X6/63
Fourth digit
Defines the controller interface for reading certain control signals (e.g. speed setpoint).
Configuration of C0005
Interface
xxx0
Control terminals
xxx1
RS 232, RS 485 or optical fibre
xxx3
INTERBUS or PROFIBUS−DP
xxx5
System bus (CAN)
2.2.1
Changing the basic configuration
If a basic configuration must be changed to meet specific requirements, proceed as follows:
1. Select a basic configuration that largely meets your requirements under C0005.
2. Add functions that are not available by:
– Changing the input and/or output configurations.
– Parameterising function blocks. (
^
)
– Adding or removing function blocks. (
^
)
Note!
If you change the signal flow of the basic configuration, e.g. by adding function
blocks, C0005 will be set to 0. "COMMON" will be displayed on the display.