2.4.56.2
Load ramp function generator
You can initialize the ramp function generator with defined values via the inputs SRFG1−SET and
SRFG1−LOAD.
l
As long as SRFG1−LOAD = HIGH, the value at SRFG1−SET is switched to SRFG1−OUT.
l
When SRFG1−LOAD = LOW, the ramp generator accelerates from this value to its input value
at SRFG1−IN via the set S−shape.