T
ROUBLE SHOOTING
6.2 Fault memory
6-13
8310/8610-8
No.
Displays B/C
Unit Axis
Description
6
Delta_s< S max -
X
Absolute value of the negative control
deviation (contouring distance) is
larger than the programmed
»S max -« maximum value; refer to
storage location 3/43
7
stop & auto cal
X
Search for reference
signal was preset
with Low level at the
stop
input or the
unit being in the interrupted state
8
reset & auto cal
X
Search for reference
signal was preset
with High level at the
reset
input
9
start & auto cal
X
Search for reference
signal was preset
with the unit being in the started state
10
m.Drive& auto cal
X
Search for reference
signal was preset
during manual positioning of the drive
11
ProgPar& auto cal
X
Search for reference
signal was preset
during the programming of machine
parameters
12
MemEdit& auto cal
X
Search for reference
signal was preset
during the recalculation of machine
parameters, i.e., directly after terminat-
ing the programming operation
13
stop & start
X
Start
signal was preset with Low level
at the
stop
input
14
reset & start
X
Start
signal was preset with High level
at the
reset
input
15
autoCal& start
X
Start
signal was preset although at
least one axis of the unit performs an
automatic reference search routine
16
m.Drive& start
X
Start
signal was preset during manual
positioning of a drive of the unit
17
ProgPar& start
X
Start
signal was preset during the
programming of machine parameters
18
MemEdit& start
X
Start
signal was preset during a
program structure change
(inserting or deleting of nominal value
sentences/programs and serial trans-
mission of already existing programs
and of machine parameters)