COMMISSIONING
FLEXYII_WSHP-IOM-1307-E
- 41 -
RUN TEST
Start unit in cooling mode
Thermodynamic readings are possible on Climatic 60 or using
manometers.
No rated values are given here. These depend on the climatic
conditions both outside and inside the building during
operation. However, an experienced refrigeration engineer
will be able to detect any abnormal machine operation.
Safety test
- Check Air pressure switch "Dirty filter" detection test: vary
the set-point value (menu page 2335 on DS60) in respect to
the air pressure value. Observe the response of the
CLIMATIC™ (menu 2332).
- Same procedure for detecting "Missing Filter" (page menu
2334) or "Air Flow Detection" (page menu 2333).
- Check the smoke detection function (if fitted).
- Check the Firestart by pressing the test button (if fitted).
- Disconnect the circuit breakers of the condensor fans and
check the high pressure cut-out points on different refrigerant
circuits.
Reverse cycle test
This test is designed to check the good operation of the 4-
way reversing valves on heat pump reversible systems. Start
the reverse cycle by adjusting the cold or hot temperature
threshold data according to the indoor and outdoor conditions
at the time of test (
menu 2222).
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......