HEATING : GAS BURNER 60 & 120 kW
FLEXYII_WSHP-IOM-1307-E
- 61 -
PRESSURE ADJUSTMENTS ON HONEYWELL
PRESSURE REGULATING VALVE TYPE VK 4125 P
Pressure regulator adjustment with 300mbar gas
supply:
- The Burner must run in High Heat mode for this check.
- Place the tube of the “accurate” manometer on the Inlet
pressure port (Figure 15) of the Gas Regulating Valve after
having loosened the screw by one turn
Check and adjust if necessary the valve Inlet pressure to
20.0mbar (G20) or 25.0mbar for Groningen (G25) or
37.0mbar for propane (G31) after gas burner ignition
(fig.16)
High Heat Injection Pressure Checks
Check and adjust if necessary the valve OUTLET pressure
to 10.4mbar (G 20) / 13.1mbar for Groningen (G25) & 34.3
mbar for propane (G31) (fig.17)
The out pressure must be measured on the pressure tap
located on the gas injector support bar to avoid the
pressure drop due to the elbow after the valve
Fig. 15
Fig. 17
Fig.16
INLET
PRESSURE
MEASURING
PORT
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......