FILTERS
FLEXYII_WSHP-IOM-1307-E
- 52 -
F
ILTER REPLACEMENT
After opening the filter access panel, lift the filter retaining log.
The filters can then be removed and replaced easily by sliding the dirty filters out and clean ones in.
The CLIMATIC controller monitors the pressure drop across the filter.
The following set points can be adjusted depeding on the installation.
“Airflow”
in page 2333 = 25Pa by default
“No filter “
in page 2334 = 50Pa by default
“Dirty Filter”
in page 2335 = 250Pa by default
The actual pressure drop measured accross the coil can be read on the Climatic Display DS60 in menu 2332
.
The following faults may be identified
-Fault code 0001 AIRFLOW FAILURE, if measured
Δ
P across the filter and coil is below the value set in page 2333
-Fault code 0004 DIRTY FILTERS, if measured
Δ
P across the filter and coil is above the value set in page 2335
-Fault code 0005
MISSING FILTERS, if measured
Δ
P across the filter and coil is below the value set in page 2334
Be Careful: do the filters' fire classification's choice according to
the local regulations
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......