VENTILATION : PULLEYS
FLEXYII_WSHP-IOM-1307-E
- 43 -
MOUNTING AND ADJUSTING PULLEYS
F
AN PULLEY REMOVAL
Remove the 2 screws and put one of them in the extraction
threaded screw.
Screw in fully. The hub and the pulley will separate from each
other.
Remove the hub and the pulley by hand without damaging
the machine.
F
AN PULLEY INSTALLATION
Clean and de-grease the shaft, hub and conical bore of the
pulley. Lubricate the screws and install the hub and pulley.
Position the screws without turning them.
Place the assembly on the shaft and screw in the screws
alternatively and evenly. Using a mallet or a hammer with a
wooden wedge, tap on the face of the hub to keep the
assembly in place. Torque the screws to 30 Nm.
Take the pulley in both hands and shake it vigorously to make
sure everything is in place.
Fill the holes with grease for protection.
NOTE: During installation, the key should never protrude out
of its groove.
After 50 operating hours, check that the screws are still in
place.
M
OTOR
P
ULLEY
I
NSTALLATION
&
R
EMOVAL
The pulley is held in position by the key and a screw located
in the groove. After unlocking, removing this screw by pulling
against the shaft spindle (if necessary, use a mallet and tap
uniformly on the hub to remove it).
To assemble, proceed in the reverse order after having
cleaned and de-greased the motor shaft and the pulley bore.
P
ULLEYS
A
LIGNMENT
After adjusting one or both of the pulleys, check the
transmission alignment using a ruler placed on the inner face
of the two pulleys.
NOTE:
The warranty may be affected if any major
modification is made to the transmission without obtaining our
agreement beforehand.
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......