MAINTENANCE DIAGNOSTIC
FLEXYII_WSHP-IOM-1307-E
- 76 -
WATER LEAKS
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
Water found in the ventilation
section
Cooling mode:
Water carried away from the coil because
of excessive airflow and speed on the
coil.
Estimate the airflow rate and check
the speed is lower than 2.8 m/s
Low air pressure in the compartment due
to a high airflow rate or a high pressure
drop before the fan
Check filter
Reduce airflow rate
Check seals around the ventilation
section
Check the door seal
Check for the presence of silicone
seals in the corners of the door and at
the bottom of the refrigeration section
bulkhead.
Water ingress in the filter
compartment
Water ingress through a leaking fresh air
hood or when running 100% fresh air
Check the seals and flanges in the
fresh air hood
Reduce the airflow rate if necessary
CLIMATIC DISPLAYS
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
Nothing is written on the screen
but it’s enlightened
Possible problem of display addressing’
Press on the three right-hand side’s
buttons at the same time during a few
seconds then reconfigure display
address setting at 32.
Nothing occurs on the unit or an
option disappeared
Possible problem of units' configuration
Check the instructions from 3811 to
3833 and reconfigure options if
necessary.
The message “no link” appears
Problem of addresses’ recognition
Disconnect the DS from the unit and
then reconnect it.
All the units are extinct
Problem main board plan addressing
Disconnect then re-plug; disconnect
each unit from the others then change
all the plan addresses
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......