• 96 •
DC60-DM60_ROOFTOP-IOM-1307-E
CONFIGURATION
Brightness / Contrast
The display is equipped with a contrast, but it can be adjusted manually. For manual adjustment of contrast, simultaneously press the
'alarm' and 'prg' keys and press 'arrow' or 'down arrow' buttons to increase or decrease the contrast.
Con
fi
guring the terminal's address
The termminal's address (DC60 or DM60) must be checked after putting the card to 'On':
• access the setup mode by pressing the 'arrow', 'enter' and 'down arrow' keys for at least 5 seconds.
• press 'enter' to place the cursor on 'setting'
• with 'arrow' or 'down arrow' set the address of the display 31 of DM60, then con
fi
rm by pressing 'enter'
The screen 'display address changed' is displayed.
If after 5 seconds the display is not correct:
• access, a second time, the setup mode by pressing the 'arrow', 'enter' and 'down arrow' keys for at least 5 seconds, up to the next
screen.
• press 'enter' to place the cursor on 'setting'
• press 'enter' a second time to place the cursor on the I / O board address line
• with 'arrow' or 'down arrow' replace '-' by the address of the BM60 connected and con
fi
rm by pressing 'enter'
FUNCTIONALITY OF THE DM60
Rooftop selection
A DM60 can be connected to 8 units per the pLan bus. DM60 screens connected, alternatively, to one of BM60.
The next screen allows selection of the unit to display:
Each of the 8 rooftops is represented by a number. The selected rooftop is indicated by its number which is framed. Each time you
press the 'down arrow' button, it connects the display to the next rooftop.
Pressing 'enter' key returns to the main screen.
DISPLAY DM60
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......