CONTROL VARIABLES
FLEXYII_WSHP-IOM-1307-E
- 72 -
Digital inputs (dry contacts)
Maximum 2 free input contacts on BM60 :
BM-J4-ID4 Not always available
BM-J4-ID7 Not always available
Maximum 4 free input contacts on BE60
BE-J4-ID1 always available
BE-J4-ID2 always available
BE-J4-ID3 always available
BE-J4-ID4 always available
Functions can be set among followings:
Power
Power of the unit (ON/OFF)
Reset Al
Reset, Alarm
Summer
Control, Unloaded heating mode
Winter
Control, Unloaded cooling mode
Low Fan
Blower, Force reduced flow (low speed)
High Fan
Blower Force nominal flow (high speed)
No F.A
Fresh Air, Force the damper to close (0%)
10% F.A
Fresh Air, Force the damper to minimum opening (10%)
20% F.A
Fresh Air, Force the damper to minimum opening (20%)
30% F.A
Fresh Air, Force the damper to minimum opening (30%)
40% F.A
Fresh Air, Force the damper to minimum opening (40%)
50% F.A
Fresh Air, Force the damper to minimum opening (50%)
All F.A
Fresh Air, Force the damper to full opening (100%)
No FreeC
Fresh Air, Unloaded Free-Cooling mode
No FreeH
Fresh Air, Unloaded Free-Heating mode
No Air.Q
Air Quality, Unloaded control
Defrost
Circuit, Defrosting cycle delayed (Compressor)
50% Cp.
Circuit, Unloaded immediately 50% of compressors
running
No Comp.
Circuit, Unloaded all compressor
No HPump
Circuit, Unloaded all compressor in heat-pump mode
No Cp&Ht
Circuit and Heaters, Unloaded all
50% Ht.
Heaters, Unloaded immediately 50% of heaters running
No Heat.
Heaters, Unloaded all heaters
Prio.Ht.
Control, Force the Priority of the heaters vs Compressors
Tcb G
TCB, G
Tcb B
TCB, B
Tcb Y1
TCB, W1
Tcb Y2
TCB, W2
Tcb W1
TCB, Y1
Tcb W2
TCB, Y2
for BMS
BMS, input reading for BMS
Sched. A
Schedule, Force the Mode A
Sched. B
Schedule, Force the Mode B
Sched. C
Schedule, Force the Mode C
Sched. D
Schedule, Force the Mode D
Sched.BMS Schedule, Force the Mode BMS
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......