INSTALLATION ON A ROOFMOUNTING FRAME
FLEXYII_WSHP-IOM-1307-E
- 19 -
When the frame is correctly positioned, it is essential to secure the assembly with a disconnected stitched welded seam (20 to
30mm every 200mm
) along the outside or by using an alternative method
CURBING AND FLASHING
Outside of frame must be insulated with rigid type insulation;
We recommend a minimum of 20 mm thick insulation (2 - figure 7).
Check that the insulation is continuous, counter flash and seal around the
frame as shown in (1-figure 7).
CAUTION: To be effective, the upstream must end below the drop edge (3 -
figure
7).
Where pipes and electrical conduits extend through the roof, flashing must
conform to local codes of practice
Before installing the equipment, make sure that seals are not damaged and check that the unit is secured to the mounting
frame. Once in position, the bottom of the equipment must be horizontal.
The installer must comply with local authority standards and specifications.
Fig. 7
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......