MAINTENANCE DIAGNOSTIC
FLEXYII_WSHP-IOM-1307-E
- 73 -
REFRIGERATION
FAULT
POSSIBLE CAUSE AND SYMPTOMS
SOLUTION
LP PROBLEMS AND LP CUT
OUTS
Refrigerant charge too low
Measure the superheat and sub-cooling
Good if 5°C<SC<10°C and 5°C<SH<10°C
Bad if SC>10°C and SH too low
Check superheat adjustment and charge
unit (a leak check must be carried out)
In Heat Pump Mode the temperature
difference between T outdoor and Tevap.
(Dew) is too high
5°C < Delta T < 10°C excellent
10°C < Delta T < 15°C acceptable
15°C < Delta T < 25°C too high
If too high check the coils are clean or
check coil internal pressure drop between
the liquid line and the suction line
Good if < 3bar
Too high > 3 bar (coil blocked)
Refrigeration circuit blocked in distribution
Stop the fan and create icing of the coil.
Check all circuits freeze evenly across the
whole surface of the coil
If some parts of the coil do not freeze this
could indicate a problem with the
distribution
Liquid line drier blocked. High temperature
difference between inlet and outlet of the
drier
Change filter drier
Contaminant in the expansion valve
Attempt to free the valve adjusting element
by freezing the valve and then heating the
thermostatic element. Replace the valve if
necessary
Expansion valve not adjusted properly
Adjust the expansion valve
Ice plug in the expansion valve
Heat the main body of the valve. If the LP
increases and then decreases gradually,
empty the circuit and replace the drier
Incorrect insulation of the thermostatic bulb
of the expansion valve
Superheat too low: adjust superheat
Move the thermostatic element along the
pipe
Insulate the Thermostatic element of the
valve
Low Pressure Switch cut out point too high
Check the cut out pressure of the Low
Pressure switch: It must be 0.7+/- 0.2bar
and must closes at 2.24 +/- 0.2 bar
LP cut out due to not enough defrost on
heat pumps
Adjust the CLIMATIC settings to extend the
defrost cycles or shorten the time between
defrosts
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......