ADVANCED SCROLL TEMPERATURE PROTECTION (ASTP)
FLEXYII_WSHP-IOM-1307-E
- 56 -
O
PERATION
M
ODE
E
XPLANATION
v
Protection is activated when Scroll Discharge Port.
Reaches
150°C
(+/- 17K)
v
Compressor is protected as « Unloaded » but
continues to run
•
Protection mode balances discharge/suction
pressure
-
Motor heat builds inside compressor
-
No refrigerant flow to carry motor heat away
v
Motor protector opens (Klyxon)
•
Compressor turns off, cools
v
Motor protector resets, compressor restarts
•
Bi-metal disk resets before motor protection
•
Cycle will continue until cause of overheat is fixed
S
ERVICE A
C
OMPRESSOR
v
What to do?
•
If a protected compressor is identified
-
Stop the compressor
-
Allow to cool thoroughly
-
Restart pump & check for normal operation
v
DO NOT ASSUME A COMPRESSOR RUNNING
UNLOADED (BALANCE PRESSURE) IS A FAILURE
v
Likely situations where protection may activate :
•
Initial system charging (or recharging after servicing)
-
Compressor is run with too little system charge
§
Very common on split system
§
Will result in very low suction pressures (<1.7
Bars)
§
Do not disable low pressure cutouts while
charging
§
Charge high-side with liquid first
•
Field servicing (system problem causes overheating)
-
Technician will observe « Balanced pressures »
-
Risk of misdiagnosis as failed compressor
-
Must stop pump, cool thoroughly, reset
Temperature Behavior with ASTP Protection
40
65
90
120
150
180
0
20
40
60
80
100
120
140
160
Time (Minutes)
T
em
p
er
at
u
re (
°C
)
DISC OPENS,
SCROLLS UNLOAD
Compressor Runs
Balanced
Pressures
PROTECTOR RESETS,
PUMP RESTARTS FULLY
LOADED
MOTOR PROTECTOR
OPENS, PUMP TURNS
OFF
Discharge
Port
Klyxon
ASTP
Compressor
off
Summary of Contents for ROOFTOP FLEXY FXK 55
Page 2: ......
Page 26: ...COMMISSIONNING FLEXYII_WSHP IOM 1307 E 24 STEP 3 Fitting STEP 4 Check SAME LEVEL 10 15 mm...
Page 36: ...COMMISSIONNING REPORT FLEXYII_WSHP IOM 1307 E 34 COMMENTS...
Page 50: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 48 AT18 18S...
Page 51: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 49 ADH355L...
Page 52: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 50 ADH450L...
Page 53: ...VENTILATION AIRFLOW BALANCING FLEXYII_WSHP IOM 1307 E 51 ADH500L...
Page 71: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 69 60kW 120kW...
Page 72: ...HEATING GAS BURNER FLEXYII_WSHP IOM 1307 E 70 180kW 240kW...
Page 105: ......