Technical data sheet
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
KNX multiapp
Parameters
Setting
Long push action min.
0.5 second
1 second
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
This parameter determines the minimum period for detecting a long
push.
add status object
Yes /
No
The parameter determines if an additional communication object (sta-
tus) shall be used to perform toggle functionality or other purposes.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes /
No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
1 x 1 unsigned byte
No.
Object name
function
Size
flags
5
(12, 19,
26, 33, 40,
47, 54, 61,
68, 75, 82,
89, 96,
103, 110)
Input G(,H)1 (2
8) Unsigned
Value
5.010
DPT_
Value_1_
Ucount
CT
The telegrams with the unsigned value are sent via the group address
linked with this object.
4
(11, 18,
25, 32, 39,
46, 53, 60,
67, 74, 81,
88, 95,
102, 109)
Input G(,H)1 (2
8) Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
They are only visible if“Add enable object”parameter value is set to yes.
Parameters
Setting
Byte value when contact is closed
0
255,
1
Here an adjustment is made to define which unsigned 8-bit value is
written into the storage cell of the communication object and sent
after a rising edge in the signal status at the channel (input). The rising
edge corresponds to a change in the signal status at the input from
logical “0” to “1”.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes / No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
2 x 1 unsigned byte
No.
Object name
function
Size
flags
5
(12, 19,
26, 33, 40,
47, 54, 61,
68, 75, 82,
89, 96,
103, 110)
Input G(,H)1 (2
8) Unsigned
Value
5.010
DPT_Va-
lue_1_
Ucount
CT
The telegrams with the unsigned value are sent via the group address
linked with this object
4
(11, 18,
25, 32, 39,
46, 53, 60,
67, 74, 81,
88, 95,
102, 109)
Input G(,H)1 (2
8) Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
They are only visible if“Add status object”parameter value is set to yes.
•
Switch
This function is used for inputs with a switch to send a byte value tele-
gram, the contact is closed or opened, a telegram is sent.
Parameters
Byte value when co
Here an adjustment
value is written into
sent after a rising edge
rising edge corresponds
from logical “0” to “1”
Byte value when co
Here an adjustment
written into the stor
after a falling edge in
falling edge corresponds
from logical “1” to “0”
Contact type
The contact type of
“Normally open con
closed, inactive whe
“Normally closed con
opened, inactive wh
add enable object
The parameter deter
Enable object or no
changes at this input
•
Push
This function is used fo
gram, the push is short
Parameters
Byte value on shor
Here an adjustment
written into the stor
after short pressing
Byte value on long push
Here an adjustment
written into the stor
after long pressing the
Long push action min
This parameter deter
push.
Contact type
The contact type of
“Normally open con
closed, inactive whe
“Normally closed con
opened, inactive wh