LEGRAND 0 484 22 Manual Download Page 20

20/29

Technical data sheet: S000074637EN-5

Updated: 12/03/2015

Created: 15/04/2014

Technical data sheet

Catalogue number(s): 0 484 22

KNX multiapplication controller 16 outputs

KNX multiapp

8. COmmUNiCa

8. COmmUNiCaTiON OBJECTS (CONTiNUED)

Parameters

Setting

Xn : Invert enable logic

Yes /

No

The Enable logic of the output attached to the channel is adjusted

here.

“No

”: the contact of the output is Disable when “Output Xn, Enable”

object value is 0.

“Yes

”: the contact of the output is Disable when “Output Xn, Enable”

object value is 1.

8.2.2 Shutter (for Ports A and B only)

No.

Object name

function

Size

flags

114,122

Outputs A (B)

Shutter Up/

Down

1.008 DPT_

UpDown

CW

The Up/Down movement for the corresponding channel is initiated via

these objects. The shutter is raised on receipt of a logical 0 and lowered

on receipt of a logical 1. The drive mechanism remains switched on

until either a stop command is received

115,123

Outputs A (B)

Open/Close

Slats

1.009 DPT_

OpenClose

CW

Shutter Stop

Via these objects, the movement of a blind/shutter is stopped

regardless of whether the telegram contains a logical 0 or a logical 1.

If the output is configured as "Venitian blind" and the blind is statio-

nary, the slats are opened by one step on receipt of a logical 0 and

closed by one step on receipt of a logical 1.

If the output is configured as "Roller shutter" and a stop command is

received when the roller shutter is stationary, the command is ignored.

117,125

Outputs A (B)

Shutter

Alarm

1.005 DPT_

Alarm

CW

This object can be linked with an alarm signal from a wind, rain or ice

detector, which sends a logical 0 in the idle state and a logical 1 in the

event of an alarm.

116,124

Outputs A (B)

Shutter

Enable

1.003 DPT_

Enable

CW

Enable telegrams are received via the group address linked with this

object. They are used to lock (disable) or unlock (enable) the correspon-

ding input.

In ventian blind use you have the parameters for slat control

Parameters

Setting

Xn+(n+1) Usage

Use separately(*)

Venitian blind

Roller shutter

Exclusive function

Slat time (base 100ms)

3

 (0

255)

Only available if “Xn+(n+1) Usage” is set to “Venitian blind”

Parameters

Setting

Up to Down time (base 1s)

30

 (0

255)

Only available if “Xn+(n+1) Usage” is set to “Venitian blind” or “Roller

shutter”

Behaviour on alarm

No action

Move up

Move down

Only available if “Xn+(n+1) Usage” is set to “Venitian blind” or “Roller

shutter”

Invert relay polarity

Yes /

No

Allows to invert the move up/down command.

“No”: X1 is move up, X2 move down

“Yes”: X1 is move down, X2 is move up

Invert Enable logic

Yes /

No

The Enable logic of the output attached to the channel is adjusted

here.

“No

”: the contact of the output is Disable when “Output Xn, Enable”

object value is 0.

“Yes

”: the contact of the output is Disable when “Output Xn, Enable”

object value is 1.

(*): See the previous parameters description and communication object

description table

8.2.3 Exclusive function (Ports A and B only)

This functionality is used to perform logical XOR functions between two

relays on the same port.

No.

Object name

function

Size

flags

115 (122)

Outputs A (B)

A2 on & A1

off | Off

(B2 on & B1

off | Off)

1.002 DPT_

Bool

CW

1 : Activates A2, Deactivates A1

0 : Deactivates A1 and A2

114 (123)

Outputs A (B)

A1 on & A2

off | Off

(B1 on & B2

off | Off)

1.002 DPT_

Bool

CW

1 : Activates A1, Deactivates A2

0 : Deactivates A1 and A2

121 (129)

Outputs A (B)

A2 Status

(B2 Status)

1.002 DPT_

Bool

CRT

1 : A2 (B2) is activated

0 : A2 (B2) is deactivated

117 (125)

Outputs A (B)

A1 Status

(B1 Status)

1.002 DPT_

Bool

CRT

1 : A1 (B1) is activated

0 : A1 (B1) is deactivated

Parameters

Setting

Xn, Invert relay polarity

Yes /

No

Allows to invert the logic of the exclusive function

8.2.4 Dali

No.

Object n

178

DALI

This object is used to

red to the DALI bus

Switching telegrams

object.

179

DALI

The current switchin

It is automatically sen

180

DALI

This object is used to

red to the DALI bus

Level value telegram

object.

181

DALI

The current level sta

automatically sent each

184

DALI

Dimming control te

with this object.

182

DALI

Enable telegrams ar

object. They are use

ding input.

183

DALI

Override telegrams

object.

Output Xn can be for

value of the commu

of the contact:

0 or 1 = The output is not f

2 = The output is for

3 = The output is for

S000074637EN-5.indd 20

20/05/15 10:16

Summary of Contents for 0 484 22

Page 1: ...tributed in each of the blocks blinds 2 blocks of 2 relays 2 1 A max to be distributed in each of the blocks and power sockets 2 blocks of 2 relays 16 A max to be distributed in each of the blocks Eac...

Page 2: ...E and F 2 blocks of 2 relays 16 A max to be distributed in each of the blocks For controlling 2 separate loads per block Each block includes energy measurement Dali output For controlling 64 DALI ball...

Page 3: ...A Power Supply 27 50 VA 6 W min L N L N L N L N L N L N L N 30 mA L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5...

Page 4: ...A 6 A 30 mA 30 mA 30 mA 6 A 10 A 10 A L N L N 30 mA L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5 110 230 VA 50...

Page 5: ...30 mA 6 A 10 A 10 A L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N 30 mA L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5 110 230...

Page 6: ...ly OFF no fault L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5 110 230 VA 50 60 Hz 6 W NC ND NE NF 0 484 22 Power...

Page 7: ...el input The rising edge corresponds to a change in the signal status at the input from logical 0 to 1 No reaction An edge change at the input does not change the object value and also does not send a...

Page 8: ...the switching value stored in the commu nication object is inverted and the new value is sent Long push action min 0 5 second 1 second 2 seconds 3 seconds 4 seconds 5 seconds 10 seconds This parameter...

Page 9: ...ine which movement command is written into the storage cell of the communication object and sent after a short press the push button attached to the input No reaction action does not change the object...

Page 10: ...Scene Number CT The telegrams to recall the scene with the configured number between 1 and 64 are sent via the group address link with this object 4 11 18 25 32 39 46 53 60 67 74 81 88 95 102 109 Inpu...

Page 11: ...w Priority Off State 01b Low Priority On State 10b High Priority Off State 11b High Priority On State Switch This function is used for inputs with a switch to send a priority telegram the contact is c...

Page 12: ...4 31 38 45 52 59 66 73 80 87 94 101 108 Input G H 1 2 8 Reset Counter 1 015 DPT_Reset CW If a telegram linked with this object is received then the counter value is reset to the minimum value set by t...

Page 13: ...tion On Off Toggle Here an adjustment is made to define which switching value is written into the storage cell of the communication object and sent after short pressing the push button attached to the...

Page 14: ...n ding input They are only visible if Add enable object parameter value is set to yes Parameters Setting Byte value when contact is closed 0 255 1 Here an adjustment is made to define which unsigned 8...

Page 15: ...to the input Byte value on long push 0 255 0 Here an adjustment is made to define which unsigned 8 bit value is written into the storage cell of the communication object and sent after long pressing...

Page 16: ...e storage cell of the communication object and sent after short pressing of the push button attached to the input No reaction A short push does not change the object value and also does not send a tel...

Page 17: ...at the channel input The falling edge corresponds to a change in the signal status at the input from logical 1 to 0 No reaction action does not change the object value and also does not send a telegr...

Page 18: ...so does not send a telegram Stop the stop command value 1 or 0 is transferred into the com munication object and sent Xn Long push action min 0 5 second 1 second 2 seconds 3 seconds 4 seconds 5 second...

Page 19: ...t They are used to lock disable or unlock enable the correspon ding input No Object name function Size flags 117 121 125 129 133 137 141 145 149 153 157 161 165 169 173 177 Output Xn 2bits Over ride 2...

Page 20: ...telegrams are received via the group address linked with this object They are used to lock disable or unlock enable the correspon ding input In ventian blind use you have the parameters for slat cont...

Page 21: ...at shall be used for the dimmer Attention this value can be overridden by the dali ballast physical minimum level Max Level 0 100 default 100 This parameter is used to set the maximum level that shall...

Page 22: ...None On or Enable On No Object name function Size flags 198 Mode_Sytem Mode_Sytem 1 010 DPT_ Start CRW 1 Enables System mode disables all other modes 0 No reaction 199 Mode_1 Mode_1 1 010 DPT_ Start C...

Page 23: ...e order action that should be executed on the output when the corresponding scene number is received Xn n 1 Delay immediate 500 ms 1 second 2 seconds 5 seconds 10 seconds 30 seconds 1 minute 90 s 2 mi...

Page 24: ...utput 3 4bytes 12 001 DPT_ Value_4_ Ucount The Program function Output 3 value is sent via the address linked with this object when the program is triggered No Object name function Size flags 218 224...

Page 25: ...ts 1 Byte 2 Bytes 4 Bytes Here it is possible to make an adjustment to set the datapoint size of the Program Fn Output Y XXX communication object Parameters Setting Output 1 2 5 value Type Input Size...

Page 26: ...Value_2_ Ucount Logic Fn Input 1 4bytes 12 001 DPT_ Value_4_ Ucount This object is used as an event to trigger the logical function Depending on the Input 1 Object size parameter this communication ca...

Page 27: ...djustment to choose which comparator should be used to compare Value 1 parameter and the value received from the bus Logic Fn Input 1 XXX Attention Due to errors of precision it s strongly recommended...

Page 28: ...lue 0 15 4 bits Dimming Up 100 Up 50 Up 25 Up 12 Up 6 Up 3 Up 1 Stop Stop Down 1 Down 3 Down 6 Down 12 Down 25 Down 50 1 Byte Non scaled value 0 255 1 Byte Scaled value 0 100 1 Byte Scene 1 64 2 Bytes...

Page 29: ...elegrams Relay contact On Off On On Off On Off Time delay Off d Delay before OFF delay before ON Switching telegrams Relay contact On Off On On Off On Off Time delay Off On Off e Auto Switch OFF Switc...

Reviews: