KNX multiapplication controller 16 outputs
8. COmmUNiCaTiON OBJECTS
8.1 inputs
Inputs can each be used as“Inputs, separately configurable”or as“Inputs,
jointly configurable". According to this setting the available functions and
objects change.
8.1.1 Use separately
Not used
Input is not usable, no accessible communication objects
Switching
The following objects are automatically inserted:
No.
Object name
function
Size
flags
2
(9, 16, 23,
30, 37, 44,
51, 58, 65,
72, 79, 86,
93, 100,
107)
Input G(,H)1 (2
8) Switching
1.001 DPT_
Switch
CWT
Switching telegrams are sent via the group address linked with this
object
3
(10, 17,
24, 31, 38,
45, 52, 59,
66, 73, 80,
87, 94,
101, 108)
Input G(,H)1 (2
8) Switching
Status
1.001 DPT_
Switch
CW
Switching states are received via the group address linked with this
object.
They are only visible if “Add status object” parameter value is set to yes.
4
(11, 18,
25, 32, 39,
46, 53, 60,
67, 74, 81,
88, 95,
102, 109
Input G(,H)1 (2
8) Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the corres-
ponding input.
They are only visible if“Add enable object”parameter value is set to yes.
•
Switch
This function is used, for binary inputs to which a switch button is atta-
ched, to send a switching telegram (ON, OFF or TOGGLE) as a reaction
to a rising and / or falling signal edge at this input. Each time the push
button is pressed and / or released resp. the contact is closed and / or
opened a telegram is sent, i.e. this function can be used e.g. to imple-
ment the behavior of a bell switch.
Parameters
Setting
Switching value when contact is closed
No reaction
On
Off
Toggle
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after a
rising edge in the signal status at the channel (input). The rising edge
corresponds to a change in the signal status at the input from logical
“0” to “1”.
“No reaction”: An edge change at the input does not change the object
value and also does not send a telegram.
“
On”: In the event of a rising edge the switching value “ON” (binary
value, “1”) is transferred into the communication object and sent.
“
Off”: In the event of a rising edge the switching value “OFF” (binary
value,”0”) is transferred into the communication object and sent.
“Toggle” : In the event of a rising edge, the switching value stored in
the communication object is inverted and the new value is sent.
Switching value when contact is
opened
No reaction
On
Off
Toggle
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after a
falling edge in the signal status at the channel (input). The falling edge
corresponds to a change in the signal status at the input from logical
“1” to “0”.
“No reaction”: An edge change at the input does not change the object
value and also does not send a telegram.
“
On”: In the event of a rising edge the switching value “ON” (binary
value, “1”) is transferred into the communication object and sent.
“
Off”: In the event of a rising edge the switching value “OFF” (binary
value,”0”) is transferred into the communication object and sent.
“Toggle” : In the event of a rising edge, the switching value stored in
the communication object is inverted and the new value is sent.
add status object
Yes /
No
The parameter determines if an additional communication object (sta-
tus) shall be used to perform toggle functionality or other purposes.
Contact type
Normally open contact
Normally closed contact
The contact type of the input connected to the channel is adjusted
here.
“Normally open contact” : the contact of the input is active when
closed, inactive when opened.
“Normally closed contact” : the contact of the input is active when
opened, inactive when closed.
add enable object
Yes /
No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 1) the status
changes at this input are not transmitted.
•
Push
the KNX cable is
correctly connected/
seconds): restoration of
phase
y switching the
power supply
H7
H8
DALI
DALI
ON/
100%/
OFF
100%/
OFF