![background image](http://html1.mh-extra.com/html/legrand/0-484-22/0-484-22_manual_1870847016.webp)
16/29
Technical data sheet: S000074637EN-5
Updated: 12/03/2015
Created: 15/04/2014
Technical data sheet
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
KNX multiapp
8. COmmUNiCa
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
Parameters
Setting
Xn - Switching value on short push
No reaction
On
Off
Toggle
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after short
pressing of the push button attached to the input.
“No reaction”: A short push does not change the object value and also
does not send a telegram.
“
On”: After short push, the switching value “ON” (binary value, “1”) is
transferred into the communication object and sent.
“
Off”: After short push, the switching value “OFF” (binary value ”0”) is
transferred into the communication object and sent.
“Toggle”: After short push, the switching value stored in the communi-
cation object is inverted and the new value is sent.
Xn - Switching value on long push
No reaction
On
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after long
pressing of the push button attached to the input.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“
On”: A long push, the switching value “ON” (binary value, “1”) is trans
-
ferred into the communication object and sent.
Xn - Dimming value on long push
Dim +
Dim –
No reaction
Here an adjustment is made to define which dimming value is written
into the storage cell of the communication object and sent after long
pressing the push button attached to the input.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“Dim +” After short push, the dimming value “Increase 100%” is trans-
ferred into the communication object and sent.
“Dim -”: After short push, the dimming value “Decrease 100%” is trans-
ferred into the communication object and sent.
Xn - Dimming value on release push
No reaction
Stop
Here an adjustment is made to define which dimming value is written
into the storage cell of the communication object when releasing the
push button after a long press.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“Stop”: When the push button is released after a long push, the dim-
ming value “Stop” is transferred into the communication object and
sent.
Xn – Long push button action min.
0.5 second
1 second
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
This parameter determines the minimum period for detecting a long
push.
Shutter 2-input
No.
Object n
2
(16, 30,
44, 58, 72,
86, 100)
Input G(,H)1
G(,H)2 (4
The movement com
with this object in o
8
(22, 36,
50, 64, 78,
92, 106)
Input G(,H)1
G(,H)2 (4
The commands“STOP
address linked with t
4
(18, 32, 46,
60, 74, 88,
102)
Input G(,H)1
G(,H)2 (4
Enable telegrams are
object. They are used
ding input.
They are only visible
•
Switch
This function is used for
telegram : the contact
Parameters
Xn - Switching valu
closed
Here an adjustment
written into the stor
after a rising edge. T
signal status at the i
“No reaction”: action
not send a telegram
“Up”: when the contac
the communication
“Down
”: when the c
into the communica
Xn - Switching valu
opened
Here an adjustment
command is written
and sent after a falling
The falling edge cor
input from logical “1
“No reaction”: action
not send a telegram
“Stop”: when the con
into the communica
Parameters
Setting
Xn+1 - Switching value on short push
No reaction
On
Off
Toggle
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after short
pressing of the push button attached to the input.
“No reaction”: A short push does not change the object value and also
does not send a telegram.
“
On”: After short push, the switching value “ON” (binary value, “1”) is
transferred into the communication object and sent.
“
Off”: After short push, the switching value “OFF” (binary value ”0”) is
transferred into the communication object and sent.
“Toggle”: After short push, the switching value stored in the communi-
cation object is inverted and the new value is sent.
Xn+1 - Switching value on long push
No reaction
On
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after long
pressing of the push button attached to the input.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“
On”: A long push, the switching value “ON” (binary value, “1”) is trans
-
ferred into the communication object and sent.
Xn+1 - Dimming value on long push
Dim + /
Dim –
No reaction
Here an adjustment is made to define which dimming value is written
into the storage cell of the communication object and sent after long
pressing the push button attached to the input.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“Dim +” After short push, the dimming value “Increase 100%” is trans-
ferred into the communication object and sent.
“Dim -”: After short push, the dimming value “Decrease 100%” is trans-
ferred into the communication object and sent.
Xn+1 - Dimming value on release push
No reaction
Stop
Here an adjustment is made to define which dimming value is written
into the storage cell of the communication object and sent when relea-
sing the push button after a long push.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“Stop”: When the push button is released after a long push, the dim-
ming value “Stop” is transferred into the communication object and
sent.
Xn+1 - Long push button action min.
0.5 second
1 second
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
This parameter determines the minimum period for detecting a long
push.
add status object
Yes /
No
The parameter determines if an additional communication object (sta-
tus) shall be used to perform toggle functionality or other purposes.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes /
No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
S000074637EN-5.indd 16
20/05/15 10:16