12/29
13/29
Technical data sheet: S000074637EN-5
Updated: 12/03/2015
Created: 15/04/2014
mber(s): 0 484 22
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
Dimming
No.
Object name
function
Size
flags
2
(9, 16, 23,
30, 37, 44,
51, 58, 65,
72, 79, 86,
93, 100,
107)
Input G(,H)1 (2
8) Switching
1.001 DPT_
Switch
CWT
Switching telegrams are sent via the group address linked with this
object.
In the process, a short push button an ON, OFF or TOGGLE telegram.
6
(13, 20,
27, 34, 41,
48, 55, 62,
69, 76, 83,
90, 97,
104, 111)
Input G(,H)1 (2
8) Dimming
3.007 DPT_
Control_
Dimming
CT
The dimming telegrams are sent to the dimming actuator via the group
address linked with this object. In the process, a long push produces
a“100% dimming”telegram. A stop command is sent when the push
button is released if“Dimming value on release push”is set to“stop’”.
7
(14, 21,
28, 35, 42,
49, 56,
63, 70, 77,
84, 91, 98,
105, 112)
Input G(,H)1 (2
8) Value Status 5.001 DPT_
Scaling
CW
The dimming status telegrams are received from the dimming actuator
via the group address linked with this object. This object is only visible
when the parameter“Add status object”is set to“yes”.
If Dimming value on long push is set to Dim+/-:
If the dimming actuator is at a dimming value between 1 and 99%, the
dimming direction last enabled is inverted and then dimmed in the new
direction. This allow several operation locations to synchronize and to
always invert the last applied dimming direction.
Note:
If this object is not linked with a group address or the last dimming
status has not been received when the push button is pressed, the
dimming direction is inverted when Dimming value on long push is set
to Dim+/-.
No.
Object name
function
Size
flags
4
(11, 18,
25, 32, 39,
46, 53,
60, 67, 74,
81, 88, 95,
102, 109)
Input G(,H)1 (2
8) Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
They are only visible if“Add enable object”parameter value is set to "Yes".
Parameters
Setting
Switching value on short push
No reaction
On
Off
Toggle
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after short
pressing the push button attached to the input.
“No reaction”: A short push does not change the object value and also
does not send a telegram.
“
On”: After short push, the switching value “ON” (binary value, “1”) is
transferred into the communication object and sent.
“
Off”: After short push, the switching value “OFF” (binary value ”0”) is
transferred into the communication object and sent.
“Toggle”: After short push, the switching value stored in the communi-
cation object is inverted and the new value is sent.
Switching value on long push
No reaction
On
Here an adjustment is made to define which switching value is written
into the storage cell of the communication object and sent after long
pressing the push button attached to the input.
“No reaction”: A short push does not change the object value and also
does not send a telegram.
“
On”: After short push, the switching value “ON” (binary value, “1”) is
transferred into the communication object and sent.
Dimming value on long push
Dim +/-
Dim +
Dim –
No reaction
Here an adjustment is made to define which dimming value is written
into the storage cell of the communication object and sent after long
pressing the push button attached to the input.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“Dim+/-”: After long push, the dimming value stored in the communi-
cation object is inverted and the new value is sent.
“Dim +”: After short push, the dimming value “Increase 100%” is trans-
ferred into the communication object and sent.
“Dim -”: After short push, the dimming value “Decrease 100%” is trans-
ferred into the communication object and sent.
Dimming value on push release
No reaction
Stop
Here an adjustment is made to define which dimming value is written
into the storage cell of the communication object and sent when relea-
sing a push button after a long press.
“No reaction”: A long push does not change the object value and also
does not send a telegram.
“Stop”: When the push button is released after a long push, the dim-
ming value “Stop” is transferred into the communication object and
sent.
e
flags
10
DPT_Va-
ue_1_
ount
CT
the group address
5
DPT_Reset
CW
the counter value is
alue”parameter.
003 DPT_
able
CW
linked with this
(enable) the correspon-
r value is set to yes.
0
which minimum is
ent” parameter, the
255
the maximum
ent” parameter, the
nt
ement
has to be incre-
bject is visible or not
ormally open contact
y closed contact
o the channel is adjusted here.
t of the input is active when
t of the input is active when
blocked via an additional
f an input is blocked (Enable value = 0) the status
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
S000074637EN-5.indd 13
20/05/15 10:16