Technical data sheet: S000074637EN-5
Updated: 12/03/2015
Created: 15/04/2014
Technical data sheet
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
KNX multiapp
8. COmmUNiCa
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
Parameters
Setting
mode
Mode 1
Mode 2
Mode 3
Mode 0 (System)
This is a virtual parameter in order to configure each mode.
Xn, Active
Yes /
No
Here it is possible to do an adjustment to make the output available or
not within the 4 different modes.
This is a very high priority, “Override” actions and “Enable” actions will
have no effect on the output if “Xn Active” is set to “No”.
With “Mode 0 (System)”, this parameter has a ReadOnly permission and
locked to “Yes”.
Xn, Action on change
None
On
Off
On
Off
On + Disable
Off + Disable
Here it is possible to make an adjustment to set an automatic order
command when mode under configuration is active.
Xn, Authorize a last manual off
Yes /
No
Here it is possible to make an adjustment to allow a last OFF order
command on Xn when “Xn, Active” parameter is set to “No” (before
output becomes unavailable).
This parameter is visible only if “Xn, Active” is set to “No” and “Xn Action
on change” is set to “None”,“On”or “On”.
No.
Object name
function
Size
flags
198
Mode_Sytem
Mode_Sytem 1.010 DPT_
Start
CRW
1 : Enables System mode, disables all other modes
0 : No reaction
199
Mode_1
Mode_1
1.010 DPT_
Start
CRW
1 : Enables mode 1, disables all other modes
0 : No reaction
200
Mode_2
Mode_2
1.010 DPT_
Start
CRW
1 : Enables mode 2, disables all other modes
0 : No reaction
201
Mode_3
Mode_3
1.010 DPT_
Start
CRW
1 : Enables mode 3, disables all other modes
0 : No reaction
Parameters
Setting
Xn, Invert relay polarity
Yes / No
Allows to invert the move DND/MUR command.
8.4 Power measure management
No.
Object name
function
Size
flags
185
(186, 187,
188)
Outputs C (D, E, F)
Energy
13.010
DPT_
ActiveEnergy
CR
The value saved into this communication object represents the measu-
red active energy.
189
(190, 191,
192)
Outputs C (D, E, F)
Energy Reset 1.010 DPT_
Start
CW
Start: resets the active energy counter
Stop: No reaction
193
(194, 195,
196)
Outputs C (D, E, F)
Power
mesure
14.56 DPT_
Value_Power
CR
The value of this communication object represents the measured
electrical power.
If the object communication “write” flag is set, the current value is
automatically sent each time the object value changes.
Parameters
Setting
Active power measure
Yes
No
This parameter is used to hide or display the communication objects
relating to power measure management.
8.5 Scenes
No.
Object n
1
Input Scene
Scenes telegrams ar
object.
The scene value affec
Each output channel can be assig
Each output channel can be assig
For Outputs A1, A2, B1, B2, those par
outputs are configur
Parameters
Xn, Scenario Numb
0 : No scenario
Xn, Scenario Order
Here it is possible to
that should be execut
number is received.
Xn, Delay
Here it is possible to
executing the order
number is received.
For Outputs A and B, those par
configured as "Roller