Technical data sheet
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
KNX multiapp
Parameters
Setting
Short push reaction
Priority High / On
Priority High / Off
Priority Low / On
Priority Low / Off
Here an adjustment is made to define which positive drive value is
written into the storage cell of the communication object and sent
after short pressing the push button attached to the input.
Long push reaction
Priority High / On
Priority High / Off
Priority Low / On
Priority low / Off
Here an adjustment is made to define which value is written into the
storage cell of the communication object and sent after long pressing
the push button attached to the input.
Long push action min.
0.5 second
1 second
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
This parameter determines the minimum period for detecting a long
push.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes / No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
•
Counting
Dimming
No.
Object n
2
(9, 16, 23,
30, 37, 44,
51, 58, 65,
72, 79, 86,
93, 100,
107)
Input G(,H)1
Switching telegram
object.
In the process, a sho
6
(13, 20,
27, 34, 41,
48, 55, 62,
69, 76, 83,
90, 97,
104, 111)
Input G(,H)1
The dimming telegra
address linked with t
a“100% dimming”te
button is released if“Dimmin
7
(14, 21,
28, 35, 42,
49, 56,
63, 70, 77,
84, 91, 98,
105, 112)
Input G(,H)1
The dimming status
via the group address
when the parameter
If Dimming value on
If the dimming actua
dimming direction last
direction. This allow
always invert the last applied
Note:
If this object is not link
status has not been
dimming direction is
to Dim+/-.
No.
Object name
function
Size
flags
5
(12, 19,
26, 33, 40,
47, 54, 61,
68, 75, 82,
89, 96,
103, 110)
Input G(,H)1 (2
8) Counting
5.010
DPT_Va-
lue_1_
Ucount
CT
The telegrams with the counter value are sent via the group address
linked with this object.
3
(10, 17,
24, 31, 38,
45, 52, 59,
66, 73, 80,
87, 94,
101, 108)
Input G(,H)1 (2
8) Reset
Counter
1.015
DPT_Reset
CW
If a telegram linked with this object is received, then the counter value is
reset to the minimum value set by the“minimum value”parameter.
4
(11, 18,
25, 32, 39,
46, 53, 60,
67, 74, 81,
88, 95,
102, 109)
Input G(,H)1 (2
8) Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
They are only visible if“Add enable object”parameter value is set to yes.
Parameters
Setting
Minimum value
0
255,
0
An adjustment is made via this parameter to define which minimum is
the minimum possible counter value.
In case of “decrement” value of “Increment decrement” parameter, the
next counter value is set to the maximum value.
Maximum value
0
255,
255
An adjustment is made via this parameter to define the maximum
which is the maximum possible counter value.
In case of “increment” value of “Increment decrement” parameter, the
next counter value is set the minimum value.
increment / Decrement
increment
Decrement
Here an adjustment is made to define if the counter has to be incre-
mented/decremented by 1 after each rising edge.
add “reset counter” Object
Yes /
No
This parameter determines if the “Reset Counter” object is visible or not
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes / No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
8. COmmUNiCa