KNX multiapplication controller 16 outputs
Parameters
Setting
Scene num. on rising edge
1
64
This parameter determines which scene (between 1 and 64) is to be
recalled on rising edge.
If value “0” is set, no scene is going to be recalled.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes / No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
Priority
No.
Object name
function
Size
flags
5
(12, 19,
26, 33, 40,
47, 54, 61,
68, 75, 82,
89, 96,
103, 110)
Input G(,H)1 (2
8)
Override
2bits
2.001
DPT_Switch_
Control
CT
The telegrams with the override commands are sent via the address
linked with this object in order to raise/lower the solar protection.
4
(11, 18,
25, 32, 39,
46, 53, 60,
67, 74, 81,
88, 95,
102, 109
Input G(,H)1 (2
8) Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
They are only visible if“Add enable object”parameter value is set to yes.
Value
Behaviour
00b
Low Priority, Off-State
01b
Low Priority, On-State
10b
High Priority, Off-State
11b
High Priority, On-State
•
Switch
This function is used for inputs with a switch to send a priority telegram,
the contact is closed or opened, a telegram is sent.
Parameters
Setting
Value when contact is closed
Priority High / On
Priority High / Off
Priority Low / On
Priority Low / Off
Here an adjustment is made to define which value is written into the
storage cell of the communication object and sent after a rising edge
in the signal status of the channel (input). The rising edge corresponds
to a change in the signal status at the input from logical “0” to “1”.
Value when contact is opened
Priority High / On
Priority High / Off
Priority Low / On
Priority low / Off
Here an adjustment is made to define which value is written into the
storage cell of the communication object and sent after a falling edge
in the signal status of the channel (input). The falling edge corresponds
to a change in the signal status at the input from logical “1” to “0”.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes / No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
•
Push
This function is used for inputs with a push button to send a priority
telegram, the push is short or long, a telegram is sent.
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
mber (between 1
oing to be recalled.
1 and 64) is to be
1 and 64) is to be
ormally open contact
y closed contact
o the channel is adjusted here.
t of the input is active when
t of the input is active when
blocked via an additional
f an input is blocked (Enable value = 0) the status
(between 1 and 64)
the value“0”, no scene