Technical data sheet: S000074637EN-5
Updated: 12/03/2015
Created: 15/04/2014
mber(s): 0 484 22
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
255)
blind” or “Roller
on
wn
blind” or “Roller
o the channel is adjusted
utput Xn, Enable”
utput Xn, Enable”
mmunication object
ctions between two
e
flags
002 DPT_
ool
CW
002 DPT_
ool
CW
002 DPT_
ool
CRT
002 DPT_
ool
CRT
8.2.4 Dali
No.
Object name
function
Size
flags
178
DALI
Switching
1.001 DPT_
Switch
CW
This object is used to receive the switching telegrams that are transfer-
red to the DALI bus in broadcast mode.
Switching telegrams are sent via the group address linked with this
object.
179
DALI
Switching
Status
1.001 DPT_
Switch
CRT
The current switching state of the channel is saved in the status object.
It is automatically sent each time the object value changes.
180
DALI
Level
5.001 DPT_
Scaling
CW
This object is used to receive the level value telegrams that are transfer-
red to the DALI bus in broadcast mode.
Level value telegrams are sent via the group address linked with this
object.
181
DALI
Level Status 5.001 DPT_
Scaling
CRT
The current level state of the channel is saved in the status object. It is
automatically sent each time the object value changes.
184
DALI
Dimming
3.007 DPT_
Control_Dim-
ming
CW
Dimming control telegrams are received via the group address linked
with this object.
182
DALI
Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
183
DALI
2bits Over
-
ride
2.001
DPT_Switch_
Control
CW
Override telegrams are received via the group address linked with this
object.
Output Xn can be forcibly operated (e.g. by a higher-level control). The
value of the communication object directly defines the forced position
of the contact:
0 or 1 = The output is not forcibly operated. (0 switched off, 1 switched on)
2 = The output is forcibly switched off.
3 = The output is forcibly switched on.
Parameters
Setting
Use Dali
Yes /
No
Yes: communication objects and parameters are visible.
No: communication objects and parameters are hidden.
Min. Level (%)
0
100 (default 5%)
This parameter is used to set the minimum level that shall be used for
the dimmer.
Attention, this value can be overridden by the dali ballast physical
minimum level.
Max. Level (%)
0
100 (default 100%)
This parameter is used to set the maximum level that shall be used for
the dimmer.
Fade rate level (%/s)
0
100 (default 10%)
This parameter is use to set the fade rate that shall be used with the
Level and switching communication objects.
Fade rate Dim (%/s)
0
100(default 10%)
This parameter is use to set the fade rate that shall be used with the
dimming communication object.
Delay before Off
immediate
, 500 ms,
1 second, 2 seconds,
5 seconds,10 seconds,
30 seconds, 1 minute, 90
s., 2 min., 10 min., 15 min.,
30 min., 45 min., 1 h, 90 min.
This parameter sets the wanted OFF delay time. A set OFF delay acts
only on the object “Output Xn, Switch”.
TimeBeforeOn
No reaction / Stop
This parameter sets the wanted ON delay time. A set ON delay acts only
on the object “Output Xn, Switch”.
Xn, Invert Enable logic
Yes /
No
The Enable logic of the output attached to the channel is adjusted
here.
“No”: the contact of the output is Disable when “DALI, Enable” object
value is 0.
“Yes”: the contact of the output is Disable when “DALI, Enable” object
value is 1.
Xn, Invert relay polarity
Yes /
No
The polarity type of the output attached to the channel is adjusted
here.
“No”: the contact of the output is closed when active, open when
inactive.
“Yes”: the contact of the output is open when active, close when
inactive.
8.3 mODE
Four modes are applicable. Each mode determines if an output should
be available or not.
An additional parameter allows to determine the action to do when the
desired mode is launched.
If an output is active, objects “Scene”, “Override”, “Enable/Disable”, “On/
Off” are usable.
If an output is inactive, the output cannot be managed by any object
as long as the current mode is active. If the additional parameter
“Authorize a last Manual Off” is set to “yes” it is possible to swich off the
output before the output locks.
The additional parameter “Authorize a last Manual Off” is only available
if output is set as inactive in the current mode and the parameter
“Action on change” is set to “none” or “On” or “on”.
Mode management is not available for Block A and B when they are
configured as " Roller shutter", "Venitian blind", "Exclusive function".
S000074637EN-5.indd 21
20/05/15 10:16