LEGRAND 0 484 22 Manual Download Page 21

20/29

21/29

Technical data sheet: S000074637EN-5

Updated: 12/03/2015

Created: 15/04/2014

mber(s): 0 484 22

Catalogue number(s): 0 484 22

KNX multiapplication controller 16 outputs

8. COmmUNiCaTiON OBJECTS (CONTiNUED)

255)

blind” or “Roller

on

wn

blind” or “Roller

o the channel is adjusted

utput Xn, Enable”

utput Xn, Enable”

mmunication object

ctions between two

e

flags

002 DPT_

ool

CW

002 DPT_

ool

CW

002 DPT_

ool

CRT

002 DPT_

ool

CRT

8.2.4 Dali

No.

Object name

function

Size

flags

178

DALI

Switching

1.001 DPT_

Switch

CW

This object is used to receive the switching telegrams that are transfer-

red to the DALI bus in broadcast mode.

Switching telegrams are sent via the group address linked with this

object.

179

DALI

Switching

Status

1.001 DPT_

Switch

CRT

The current switching state of the channel is saved in the status object.

It is automatically sent each time the object value changes.

180

DALI

Level

5.001 DPT_

Scaling

CW

This object is used to receive the level value telegrams that are transfer-

red to the DALI bus in broadcast mode.

Level value telegrams are sent via the group address linked with this

object.

181

DALI

Level Status 5.001 DPT_

Scaling

CRT

The current level state of the channel is saved in the status object. It is

automatically sent each time the object value changes.

184

DALI

Dimming

3.007 DPT_

Control_Dim-

ming

CW

Dimming control telegrams are received via the group address linked

with this object.

182

DALI

Enable

1.003 DPT_

Enable

CW

Enable telegrams are received via the group address linked with this

object. They are used to lock (disable) or unlock (enable) the correspon-

ding input.

183

DALI

2bits Over

-

ride

2.001

DPT_Switch_

Control

CW

Override telegrams are received via the group address linked with this

object.

Output Xn can be forcibly operated (e.g. by a higher-level control). The

value of the communication object directly defines the forced position

of the contact:

0 or 1 = The output is not forcibly operated. (0 switched off, 1 switched on)

2 = The output is forcibly switched off.

3 = The output is forcibly switched on.

Parameters

Setting

Use Dali

Yes /

No

Yes: communication objects and parameters are visible.

No: communication objects and parameters are hidden.

Min. Level (%)

0

100 (default 5%)

This parameter is used to set the minimum level that shall be used for

the dimmer.

Attention, this value can be overridden by the dali ballast physical

minimum level.

Max. Level (%)

0

100 (default 100%)

This parameter is used to set the maximum level that shall be used for

the dimmer.

Fade rate level (%/s)

0

100 (default 10%)

This parameter is use to set the fade rate that shall be used with the

Level and switching communication objects.

Fade rate Dim (%/s)

0

100(default 10%)

This parameter is use to set the fade rate that shall be used with the

dimming communication object.

Delay before Off

immediate

, 500 ms,

1 second, 2 seconds,

5 seconds,10 seconds,

30 seconds, 1 minute, 90

s., 2 min., 10 min., 15 min.,

30 min., 45 min., 1 h, 90 min.

This parameter sets the wanted OFF delay time. A set OFF delay acts

only on the object “Output Xn, Switch”.

TimeBeforeOn

No reaction / Stop

This parameter sets the wanted ON delay time. A set ON delay acts only

on the object “Output Xn, Switch”.

Xn, Invert Enable logic

Yes /

No

The Enable logic of the output attached to the channel is adjusted

here.

“No”: the contact of the output is Disable when “DALI, Enable” object

value is 0.

“Yes”: the contact of the output is Disable when “DALI, Enable” object

value is 1.

Xn, Invert relay polarity

Yes /

No

The polarity type of the output attached to the channel is adjusted

here.

“No”: the contact of the output is closed when active, open when

inactive.

“Yes”: the contact of the output is open when active, close when

inactive.

8.3 mODE

Four modes are applicable. Each mode determines if an output should

be available or not.

An additional parameter allows to determine the action to do when the

desired mode is launched.

If an output is active, objects “Scene”, “Override”, “Enable/Disable”, “On/

Off” are usable.

If an output is inactive, the output cannot be managed by any object

as long as the current mode is active. If the additional parameter

“Authorize a last Manual Off” is set to “yes” it is possible to swich off the

output before the output locks.

The additional parameter “Authorize a last Manual Off” is only available

if output is set as inactive in the current mode and the parameter

“Action on change” is set to “none” or “On” or “on”.

Mode management is not available for Block A and B when they are

configured as " Roller shutter", "Venitian blind", "Exclusive function".

S000074637EN-5.indd 21

20/05/15 10:16

Summary of Contents for 0 484 22

Page 1: ...tributed in each of the blocks blinds 2 blocks of 2 relays 2 1 A max to be distributed in each of the blocks and power sockets 2 blocks of 2 relays 16 A max to be distributed in each of the blocks Eac...

Page 2: ...E and F 2 blocks of 2 relays 16 A max to be distributed in each of the blocks For controlling 2 separate loads per block Each block includes energy measurement Dali output For controlling 64 DALI ball...

Page 3: ...A Power Supply 27 50 VA 6 W min L N L N L N L N L N L N L N 30 mA L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5...

Page 4: ...A 6 A 30 mA 30 mA 30 mA 6 A 10 A 10 A L N L N 30 mA L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5 110 230 VA 50...

Page 5: ...30 mA 6 A 10 A 10 A L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N 30 mA L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5 110 230...

Page 6: ...ly OFF no fault L 4 3 2 1 L 1 2 3 4 L 1 2 1 2 3 4 8 7 6 5 1 2 1 2 DA DA 12 V 128 mA 27 50 V Made in France A B C D E L 1 2 F DALI G H 1 2 3 4 8 7 6 5 110 230 VA 50 60 Hz 6 W NC ND NE NF 0 484 22 Power...

Page 7: ...el input The rising edge corresponds to a change in the signal status at the input from logical 0 to 1 No reaction An edge change at the input does not change the object value and also does not send a...

Page 8: ...the switching value stored in the commu nication object is inverted and the new value is sent Long push action min 0 5 second 1 second 2 seconds 3 seconds 4 seconds 5 seconds 10 seconds This parameter...

Page 9: ...ine which movement command is written into the storage cell of the communication object and sent after a short press the push button attached to the input No reaction action does not change the object...

Page 10: ...Scene Number CT The telegrams to recall the scene with the configured number between 1 and 64 are sent via the group address link with this object 4 11 18 25 32 39 46 53 60 67 74 81 88 95 102 109 Inpu...

Page 11: ...w Priority Off State 01b Low Priority On State 10b High Priority Off State 11b High Priority On State Switch This function is used for inputs with a switch to send a priority telegram the contact is c...

Page 12: ...4 31 38 45 52 59 66 73 80 87 94 101 108 Input G H 1 2 8 Reset Counter 1 015 DPT_Reset CW If a telegram linked with this object is received then the counter value is reset to the minimum value set by t...

Page 13: ...tion On Off Toggle Here an adjustment is made to define which switching value is written into the storage cell of the communication object and sent after short pressing the push button attached to the...

Page 14: ...n ding input They are only visible if Add enable object parameter value is set to yes Parameters Setting Byte value when contact is closed 0 255 1 Here an adjustment is made to define which unsigned 8...

Page 15: ...to the input Byte value on long push 0 255 0 Here an adjustment is made to define which unsigned 8 bit value is written into the storage cell of the communication object and sent after long pressing...

Page 16: ...e storage cell of the communication object and sent after short pressing of the push button attached to the input No reaction A short push does not change the object value and also does not send a tel...

Page 17: ...at the channel input The falling edge corresponds to a change in the signal status at the input from logical 1 to 0 No reaction action does not change the object value and also does not send a telegr...

Page 18: ...so does not send a telegram Stop the stop command value 1 or 0 is transferred into the com munication object and sent Xn Long push action min 0 5 second 1 second 2 seconds 3 seconds 4 seconds 5 second...

Page 19: ...t They are used to lock disable or unlock enable the correspon ding input No Object name function Size flags 117 121 125 129 133 137 141 145 149 153 157 161 165 169 173 177 Output Xn 2bits Over ride 2...

Page 20: ...telegrams are received via the group address linked with this object They are used to lock disable or unlock enable the correspon ding input In ventian blind use you have the parameters for slat cont...

Page 21: ...at shall be used for the dimmer Attention this value can be overridden by the dali ballast physical minimum level Max Level 0 100 default 100 This parameter is used to set the maximum level that shall...

Page 22: ...None On or Enable On No Object name function Size flags 198 Mode_Sytem Mode_Sytem 1 010 DPT_ Start CRW 1 Enables System mode disables all other modes 0 No reaction 199 Mode_1 Mode_1 1 010 DPT_ Start C...

Page 23: ...e order action that should be executed on the output when the corresponding scene number is received Xn n 1 Delay immediate 500 ms 1 second 2 seconds 5 seconds 10 seconds 30 seconds 1 minute 90 s 2 mi...

Page 24: ...utput 3 4bytes 12 001 DPT_ Value_4_ Ucount The Program function Output 3 value is sent via the address linked with this object when the program is triggered No Object name function Size flags 218 224...

Page 25: ...ts 1 Byte 2 Bytes 4 Bytes Here it is possible to make an adjustment to set the datapoint size of the Program Fn Output Y XXX communication object Parameters Setting Output 1 2 5 value Type Input Size...

Page 26: ...Value_2_ Ucount Logic Fn Input 1 4bytes 12 001 DPT_ Value_4_ Ucount This object is used as an event to trigger the logical function Depending on the Input 1 Object size parameter this communication ca...

Page 27: ...djustment to choose which comparator should be used to compare Value 1 parameter and the value received from the bus Logic Fn Input 1 XXX Attention Due to errors of precision it s strongly recommended...

Page 28: ...lue 0 15 4 bits Dimming Up 100 Up 50 Up 25 Up 12 Up 6 Up 3 Up 1 Stop Stop Down 1 Down 3 Down 6 Down 12 Down 25 Down 50 1 Byte Non scaled value 0 255 1 Byte Scaled value 0 100 1 Byte Scene 1 64 2 Bytes...

Page 29: ...elegrams Relay contact On Off On On Off On Off Time delay Off d Delay before OFF delay before ON Switching telegrams Relay contact On Off On On Off On Off Time delay Off On Off e Auto Switch OFF Switc...

Reviews: