DOUBLE LEAF DOOR SET
To manage the operation of a swing door with two leaf two operators is needed, one must be configured as Master and the other must
be configured as a Slave.
In the case of overlapping leaf, the operator applied to the door leaf that overlap the other (the one that opens first) must be configured
as Master.
When double swing door with overlapped leaf is used as escape route too, the installer must check that force required to
open the door manually with the slave operator 's leaf ( with Master operator's leaf overlapped) not exceed 150 N , measured
at the leading edge at right angles to the door leaf and at a height of 1000 +/- 10 mm.
In case of force over 150 N only the leaf of the Master operator must be use as escape route and consequently the
identification symbol must be put just on this leaf."
26.1)
ELECTRICAL WIRING FOR A DOUBLE LEAF DOOR SET
Make the electrical connections at the operators (see Section 12 "Electrical connections"), taking in to account that all the devices used
to open the door, the program switch and the electric lock must be connected to the Master operator.
Safety sensors installed on the master leaf must be connected to the operator Master, safety sensors installed on the slave leaf must
be connected to the Slave operator.
If the door has a double electric lock to lock each door individually, connect the electric lock that blocking the slave door at the slave operator.
Master and Slave operators must be connected together with the WR5MS wiring cable.
Connect the two terminals of the cable to connector J7 on the L-NEP logic card.
The digital programmer N-DSEL must be connected to the Master operator.
WIRING
OPERATOR MASTER
WR5MS
OPERATOR SLAVE
SAFETY
SAFETY
SENSORS
SENSORS
POWER
PROGRAM
OPENING
OPEN
START
SUPPLY
SELECTOR
RADAR
COMMAND
COMMAND
LINE
ELECTRO-LOCK
MASTER
SLAVE
WING 1 (MASTER)
WING 2 (SLAVE)
26.2)
DOOR SET UP
After completing the mechanical installation and after that electrical connections are made, manually check that the movement of both
leaves is friction-free for all the stroke
.
Before power up the operator set the switch SW1 on the logic board L-NEP as indicated on the following table.
SW1 DIP 1
SW1 DIP 2
L-NEP MASTER OPERATOR
OFF
OFF
L-NEP SLAVE OPERATOR
ON
OFF
47