Installation Checklist
1. Excavate area to receive the floor unit, ensure the hole is at least 550mm long x 150mm wide
and 140mm deep.
2. Excavate the floor for the conduit run or have a conduit route planned between the control
panel and the floor drive.
3. Mount the control panel internally within 10m of the floor operator location, with provision of a
5A switch fused spur located within 1500mm of the control panel location.
4. Install the floor operator into the floor cut out, following the instructions in this manual. Firstly
fix the cradle, then place and fix the drive unit into the cradle.
5. Plumb down from the top centre to ensure the pivot point of the floor operator is in the correct
position.
6. Install the Adaptaflex conduit between the control panel and floor operator ensuring there is a
draw cable already pulled into the conduit. Having as few bends as possible with large radius
in the bends will assist when pulling in the motor and encoder cables, (motor and encoder
cables can be prewired in place of the draw cable).
7. Pull in the motor and encoder cables leaving approx. 1m of cables at both the control panel
and floor operator locations for connection.
8. To connect the motor and encoder cable in the floor operator box, remove the stainless steel
cover, remove the primary steel cover, lift back the black neopreme seal and you will find both
cables ready for connection.
9. Once connected, carefully replace neopreme seal, fix primary steel cover into place, fix
stainless steel cover plate into place.
10. Mount door onto floor operator and top pivot and ensure the door is free swinging from 0
degrees to 130 degrees open. It is critical there are is
n’t anything inhibiting the door through its
opening and closing stroke.
11. Fix physical stops in the door closed position and the fully open position.
12. Run the cables for any auxillary products to be incorporated into the system (activation, safety
sensors, key switches etc)
13. Fix auxillary products
14. Connect and commission to EN16005
15.
Attach ‘Automatic door’ and ‘Keep Clear’ stickers in relevant areas of door
Please be aware it is not advised to fix handles on automatic doors. It is strongly recommended
should pull handles be fitted to the door, they do not exceed 1/3 of the height of the door and
centrally located to ensure they do not interfere with safety sensor operation.
Care must be taken when connecting the conduit to the gland on the floor operator, this is the only
area where water may penetrate and all warrantees will be null and void if water ingress is found
from this location.