21)
MAINTENANCE
To enter, type 10-
character technical password (for more information, refer to “Password management” paragraph).
Access to this section only for setting to zero the errors in the events memory, for setting to zero the partial counter of opening/closing
cycles performed by the door and for deleting the initial set-up performed when operation starts.
The reset of events memory and partial counter must be performed by specialized personnel only during routine maintenance, after
performing all checks on system operation.
Never delete set-up.
Only in case of leaf stroke change, reuse of operator or L-NEP logic board in a new system or if the spring needs to be
reloaded (unloaded during arm extraction because spring preload lock procedures have not been properly performed), it is
necessary to delete set-up and proceed to a new set-up following operations described in par. 14.4 (for single-leaf door) or
par. 26.2 (for double-leaf door).
The buttons in this section are used as follows:
ν
button allows forwarding in reset type selection.
^
F2
button allows returning to previous reset.
F1
(OK) button allows confirming data zero-set operation for the reset type selected.
F3
button is only used with two-leaf swing door and the symbol on the top right side of display shows M if reset operations are
relevant to
Master operator, or S if Slave operator is involved.
Every touch on
F3
button allows shifting from M to S and vice versa.
In case of single-leaf automation, letter M is shown on the top right side of display.
22)
ELECTRIC LOCK APPLICATION
To block the door in closing position, Neptis SMP operator is ready to drive an electric strike, an electric lock or an magnetic lock.
22.1) ELECTRIC LOCK / ELECTRIC STRIKE
Functions settings to activate electric lock:
F04 = ON
to activate electric lock output
F05 = OFF
to enable impulsive driving.
F06 = ON
If automatic release of electric lock is required when door is closed, with the work
program mode set to “Manual”, so to predispose door to be opened manually.
If digital programmer N-DSEL is used it's possible activate the automatic
release of electric lock at the end of closing stroke, also in the automatic work
programs. Push F2 button on N-DSEL programmer to activate the function (F2
symbol appear on display).
Push again F2 button on N-DSEL programmer to disactivate the function (F2
symbol disappear on display).
P09
Adjust the speed of the door in the last degrees of the closing stroke to facilitate electric lock coupling.
P10
Power during the 0,5 seconds of stroke on closing before opening to release electric lock.
At 0% value the function is disabled, between 01 to 100% the power increase proportionally.
P11
Delay between electric lock and motor activation in opening.
At 0% value the function is disabled, between 01 to 100% the power increase proportionally until 4 seconds.
42