IM-A-1048H
43
FUNCTION
SELECTING
MODE
Key operation and WGA-680A movement
in SETTING mode
Functional description,
supplements
F-08
Additional value Set the additional value and
press the SET key.
Range: ±99999 (Initial value: 0)
The sum of the measured value and pre-set value is
displayed.
To display the pre-set value on the indicator, execute the
DIGITAL ZERO function with the additional value being
set.
A function that adds the
desired numeric value to
the measured value for
displaying.
F-09
Automatic
ZERO
compensation
(See below figures)
(1) ZERO compensation range
Set the value and press
the SET key.
Range: 0 to 99999 (Initial value: 0)
(2) Determination time
Set the time and press
the SET key.
Range: 0.0 to 9.9 (sec.) (Initial value: 0.0)
(3) Zero-near-zero
Set the value and press
the SET key.
Range: 0 to 9 (Initial value: 0)
Zero tracking
When the
determination time is
passed and the
absolute value of the
measured value is
within the zero
compensation range,
this function executes
the DIGITAL ZERO
function and
automatically makes
the indicated value
"0".
Zero-near-zero
When the measured
value is within the
zero-near-zero range,
this function
automatically makes
the indicated value
"0".
F-10
Hysteresis
Set the value and press the SET key.
Range: 0 to 99999 (Initial value: 0)
A function that sets the
common hysteresis to four
comparators.
F-11
BCD output
Logic
For details, see separate volume of
"INSTRUCTION MANUAL (FOR BCD/RS-232C/
RS-485/TEDS OPTIONS) ".
BCD/TEDS model only.