IM-A-1048H
14
3-4. TO CONNECT [INPUT] TERMINALS
Connection of [INPUT] terminals are as
follows.
COM
: Common
1
: ZERO command
2
: HOLD command
3
: RESET command
To connect an external switch, open
collector, etc. to each [INPUT] terminal,
connect as described in the right figure.
Connect cables as follows.
1) Strip off the coating of the wire for approx. 11 mm and
twist the tip of the wire for not to loosen.
The available wire ranges are as follows.
Stranded wire : 0.2 mm
2
(AWG24) to
1.25 mm
2
(AWG16)
2) Press the lower button strongly by using the accessory
flat-head screw driver as described in the right figure.
3) Carefully insert the twisted wires into the upper hole.
4) Remove the flat-head screw driver from the lower
button. And pull the wires gently to check if they are
securely inserted.
3-5. TO CONNECT [OUTPUT] TERMINALS
Connection off [OUTPUT] terminals
are as follows.
COM
: Common
1
: [HH] output (comparator-3 output)
2
: [HI] output (comparator-1 output)
3
: [OK] output
4
: [LO] output (comparator-2 output)
5
: [LL] output (comparator-4 output)
The [OUTPUT] terminals are
open collector.
(Capacity: 30 VDC, 20 mA max)