IM-A-1048H
37
4-11. ANALOG OUTPUT (D/A) FUNCTION
The ANALOG OUTPUT function converts the measured value to the output signal (voltage): ±10V or output
signal (current): 4 to 20mA.
When the output signal (voltage) is 0 to 10 V, the output is 4 to 20 mA fixed.
a) Key operation
Press the FUNCTION key for 2 seconds. The "F-01" is displayed and FUNCTION SELECTING mode is
activated.
The mode goes to ANALOG OUTPU SETTING mode.
b) Scaling analog output voltage
Select manual setting or automatic setting.
In the manual setting, set the indicated value to output the voltage 0 V and 10 V.
In the automatic setting, the indicated value for outputting 0 V and 10 V, will be set automatically when
calibration is executed.
0 : Manual setting
1 : Automatic setting
When you select automatic setting, "F-06" is displayed. Execute procedure e, and exit the setting.
c) To set 0-V values
Set the indicated value to have the output to "0 V" or "4 mA".
The current 0-V value is displayed and the highest-order digit flickers.
d) To set 10-V values
Set the indicated value to have the output to "10 V" or "20 mA".
The current 10-V value is displayed and the highest-order digit flickers.
e) To exit
The "F-06" is displayed. Press the CANCEL key.