KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 68 -
3.5 Learning the lower limit switch
1.)
Enter YES in the menu.
2.) Move the limit switch position DOWN (100mm
over flush) with the return control. Elevator stops
on reaching the positon.
The ANTSsafe limit switch DOWN position is auto-
matically saved!
Note: From now on the SiKr is closed, if
the elevator is not in the limit switch!
3.6 Entry Distance – Lower Delay Control Point
Enter and change the value,
OFF, 2 to 500 cm;
Can be changed later -
.
possible in inspection
mode or return to safe state
Vnenn: 1,6 m/s -> 300 cm
Vnenn: 2,0 m/s -> 350 cm
Vnenn: 2,5 m/s -> 400 cm
ANTSsafe
Delay control down was stored.
3.7 Entry Distance – Upper delay control point
Enter value and change OFF, 2 to 500 cm; Can be
changed later - possible in inspection mode or re-
turn to safe condition
Vnenn: 1,6 m/s -> 300 cm
Vnenn: 2,0 m/s -> 350 cm
Vnenn: 2,5 m/s -> 400 cm
ANTSsafe
Delay Contro Top has been saved!
Note:
(setup-3 means that all ASA parameters
have been configured but no floors have been
learned into the ASA)
Note:
If DSK is active, i. the floors have already
been taught-in in the D613 and the flush levels are
set then: ENTER ->STEP-3 key otherwise:
DOWN
key