KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 45 -
Connection of the Car-Door-Contacts
The terminals are
6 and 6A / 6A and 6B / 6B and 6C.
85
Connection of the Car-Light
Attention! The connection of the cabin light must only be carried out in a voltage-free
state!
The terminal for the connection of the cabin light can be found on the circuit board X11 /,
(
Circuit diagram sheet 3 of 8 / column 3).
The terminals are
L51 (230V AC), PE and N.
Connection of the Car-Fan
The terminal for connection of the cabin fan can be found on the
circuit board X11 /,
(Circuit diagram sheet 3 of 8 / column 3).
The terminals are
L54 (230V AC), PE and N.
87
Connection of the Powersupply of Loadmeasurement-
Unit / Photocells
The connection of the supply voltage of the Loadmeasurement device (230V AC) may
only be carried out in a voltage-free state!
(Circuit diagram sheet 3 of 8 / column 3
).
The terminals are
L40 (230V AC), PE and N.
88
Connection of the Powersupply Door-Engines 230V AC
Attention! The connection of the supply voltage of the door drive unit (230V AC) may only
be carried out in a voltage-free state! The terminal for the connection of the light grating
can be found on the printed circuit board X11 /,
(
Circuit diagram sheet 2 of 8
).
The terminals are
L20 (230V AC), PE and N
.
In addition, there are 2 IP65 sockets in black for Siemens AT drives in the inspection box!
89
Connection of the Door-Commands for 3 Door
Attention! Observe page 2 of 8 in the set and follow the wiring of the terminals!
V24V DC
200
Door 1 OPEN
701
Door 1 CLOSE
702
Common Relay-Contact Door 1
703
Door 2 OPEN
704
Door 2 CLOSE
705
Common Relay-Contact Door 2
706
GND 0V DC
500
Door 3 OPEN
771
Closer-Contact Door 3 OPEN
772
Door 2 CLOSE
774
Closer-Contact Door 3 CLOSE
775