KW Aufzugstechnik GmbH Inbetriebnahme DAVID-613
DAVID-D613-Inbetriebnahme-V124-EE 18.02.2022 Seite - 12 -
20A
Hydraulic - Connection of the Valve-Wires
The connection of the valve line may only be carried out in a voltage-free state! The terminal for
the connection of the valves can be found on the terminal block X1 /
(wiring diagram sheet 1 of
8)
. Check the valve voltage according to the rating plate and the data in the circuit diagram! For
DC voltage, Valves must be equipped with varistors!
BUCHER
LRV &
iValve
Valve-Wire 1
1
Valve
UP
721
2
Valve
UP
Common
723
PE Earth
PE
Valve-Wire 2
1
Valve
DOWN
722
2
Valve
DOWN
Common
724
PE Earth
PE
4-Ventilkopf
, wie ALGI, Leistritz,
Blain, ...
Bei
3-Ventilkopf
sind die ent-
sprechenden Adern zu brücken!
Valve Fast
UP
721
Valve Slow
UP
723
Valve Fast
DOWN
722
Valve Slow
DOWN
724
Common Connection
720
Earth
PE
21A
Hydraulic - Optional - Connection of the Lower- /
Overpreasure-Contacts of the Aggregat
In the case of controlled hydraulic blocks, the evaluation is usually carried out via the
control electronics - see wiring diagram page 1 of 8!
Attention! The connection of the low / high pressure contact may only be carried out in
the de-energized state (230V AC)!
The terminal for connection is located on the printed circuit board X1 /
(Wiring diagram sheet 4 of 8).
The terminals are
1F and 1G.
17B
Rope – Connection of the Brake-Coil-Wire(s)
Attention! The connection of the brake line may only be carried out in a voltage-free state! The
terminal for connection is located on circuit board X1 / (
circuit diagram sheet 1 of 8).
Common Connection of the
brake coils
+ Brake coil pos. Voltage
721
- Brake coil 0V
720
Earth
PE
Separate Connection of the
brake coils (MRL)
+ 1.
Brake coil pos. Voltage
721
+ 2.
Brake coil pos. Voltage
722
- Brake coils 0V
720
Earth
PE
Check the brake voltage according to the brake type plate and the data in the wiring diagram!
Ensure proper interference of the magnet coil -> varistor, RC-erase, free-wheeling diode ....
18B
Rope – Connection of the Motor-Wire
Attention! The connection of the motor cable must only be carried out in a voltage-
free state!
The motor cable is already installed in the control unit as standard for all KW controls.
It is designed as a flexible cable. In the case of frequency-controlled systems, the ca-
ble is equipped with a CU shield, which must be placed in a metal fitting on the motor
clamping box. If there is no metal screw connection, the shield must be twisted and
connected to the PE terminal (Pig-tail shielding) and a metal screw connection must
be installed immediately!
19B
Mounting & Connection of the Brake-Resis-
tor
Attention! The connection of the brake resistor may only be carried out in a voltage-
free state!
The brake resistor wire is already installed in the control system as standard for all
KW controllers. It is designed as a shielded cable. The screen must be connected to
the cable clamp. The cable must be shortened if necessary and should not be placed
in squiggles (EMC interference!).