R60047.0002 - Index 2
EN – page 103 / 115
16.6
EDM: 2 external relays at X4 with SIL3
Precondition: 2 relays, 3 control outputs, 2 control inputs, auxiliary contact NO:
Parameter
Setting Description
„Switch Mode OUT1“
9
OUT1 to generate clock signal
„Switch Mode OUT2“
0
OUT2 to signal overspeed
„Switch Mode OUT3“
0
OUT3 to detect overspeed
„Read Back OUT“
6
Inversion (connection via NO contact)
„IN3 Function“
18
Adaption to OUT2 (overspeed)
„IN3 Config“
12
Adaption to clock output OUT1 (via X24/2 contact)
„/IN3 Function“
19
Adaption to OUT3 (overspeed)
„/IN3 Config“
13
Adaption to clock output /OUT1 (via X24/3 contact)
„Input Mode 2“
2
4 single control inputs for free use
„Read Back Delay“
0,050
Delay 50 ms to obviate contact bouncing
„Output Mode“
0
Inverse operation
Function:
This application uses two independent outputs /OUT2 and /OUT3 with fully
identical configuration concerning their switching characteristics. The basic
function is similar to the application with one relay. The auxiliary contacts of
both relays are individually connected to a separate input each. The GND lines of
the two relays must be independent one from each other (Safety Integrity Level
= 3).
The main contacts can be used as opener or closer depending on the application.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...