R60047.0002 - Index 2
EN – page 98 / 115
16.1
EDM: 1 external relay on x4 with SIL1
Precondition: 1 relay, 2 control outputs, 1 control input, auxiliary contact NO:
Parameter
Setting
Description
„Switch Mode OUT1“
0
OUT1 to detect overspeed
„Switch Mode OUT2“
9
OUT2 to generate clock signal
„Read Back OUT“
1
Inversion (connection to /OUT1 via NO contact)
„IN3 Function“
17
Adaption to OUT1 (overspeed)
„IN3 Config“
14
Adaption to clock output OUT2 (via X24/2 contact)
„Input Mode 2“
2
4 single inputs for free use
„Read Back Delay“
0,050
Delay 50 ms to obviate contact bouncing
„Output Mode“
0
Inverse configuration
Function:
With normal operation speed the inverted output /OUT1 is in HIGH state and the
relay is energized. The forcibly guided aux. contact therefore is closed and the
clock signal is conducted to the input. Upon overspeed output /OUT1 will
descend to LOW and the remote relay will drop.
Errors in the clock circuit can only be detected while the relay is energized. Under
error condition the SMCx monitor will set all digital outputs to LOW, i.e. the
remote relay will be de-energized, which will signal “overspeed”. With errors
occurring under normal operating speed, the unit will take an error state which
signals “overspeed” again (Safety Integrity Level = 1).
The main contacts can be used as opener or closer depending on the application.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...