R60047.0002 - Index 2
EN – page 22 / 115
5.6
Analog output 4 to 20 mA
A safety- related analogue output is available at terminal strip [x5 | ANALOGUE OUT].
The current output is freely scalable by setting parameters “Analog Start” and “Analog
End”.
If the analogue output is not used, [X5:2] and [X5:3] must be bridged. An error is
detected when the analogue output is open (e.g. wire breakage).
In the normal state, the output signal moves in the range between 4 and 20 mA.
In case of an error, the analogue output is controlled by 0 mA.
The connection of the analog output is only safe if the following device can detect the
fault condition of the safety device.
The terminal [X5] provides 9 connections:
[X5 | ANALOG OUT]
Analog out
[X4:2-3]
[X5 | ENCODER OUT]
HTL / RS422-Output
[X4:4-9]
Pluggable 9-pole terminal [X5]
•
If the analogue output is not used, [X5:2] and [X5:3] must be
bridged.
•
An error is detected when the analogue output is open (e.g. wire
breakage).
•
In case of an error, the analogue output is controlled by 0 mA.
•
The Safety Integrity Level (SIL) or the Performance Level (PL) is
reduced if only the analog output is connected. A parallel
connection of splitter and relay output or switching output is
necessary to reach SIL3/PLe.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...