Parameter Description
Factory
setting
Setting
Unit
Access level
Possible settings
EP
MP
Min.
Max.
3-3-2-7
Rated I
²
t
Nominal value, I2t
100
100
100
150
-
Factory
-
3-3-4
Start Adjust
Submenu for
displaying startup
settings
-
-
-
-
-
-
-
3-3-4-1
Start Delay
Selection of start
time delay
0.1
0.1
0
60
s
Customer
-
3-3-4-2
Start Out Freq
Selection of start
output frequency
0
0
0
10
%
Customer
-
3-3-5
Motor Temp
Submenu for
displaying motor
temperature
-
-
-
-
-
-
-
3-3-5-1
Thermal Protect
Activate/deactivate
thermal motor
protection
2
2
-
-
-
Customer
No Protection
PTC Protection
3-3-5-2
Thermal Limit
Selection of limit
value of thermal
motor protection
83.5
83.5
0
100
%
Service
-
3-3-6
Ramps
Ramps
-
-
-
-
-
-
-
3-3-6-1
Ramp 0 up/down
Ramp used to reach
minimum frequency
from 0 and vice
versa
3
3
0.5
600
s
Customer
-
3-3-6-2
Ramp 1 Up-tm
Ramp 1 used to go
from start frequency
to setpoint
frequency
3
3
0.5
600
s
Customer
-
3-3-6-3
Ramp 1 Down-tm
Ramp 1 used to go
from setpoint
frequency to stop
frequency
3
3
0.5
600
s
Customer
-
3-3-6-4
Ramp 2 Up-tm
Ramp 2 used to go
from start frequency
to setpoint
frequency
3
10
0.5
600
s
Customer
-
3-3-6-5
Ramp 2 Down-tm
Ramp 2 used to go
from setpoint
frequency to stop
frequency
3
10
0.5
600
s
Customer
-
3-3-6-6
R1/2 Start Freq
Frequency to
change from ramp 0
to ramp 1/2
50
50
0
100
%
Customer
-
3-3-6-7
R1/2 Stop Freq
Frequency to
change from ramp
1/2 to ramp 0
50
50
0
100
%
Customer
-
10 Parameter lists
PumpDrive
113 of 162