Parameter Description
Factory
setting
Setting
Unit
Access level
Possible settings
EP
MP
Min.
Max.
3-11-3-1
Prop Const
Proportional gain of
current limitation
control
10
10
0
100
Factory
-
3-11-3-2
Integral Const
Integral term of
current limitation
control
2
2
0
100
-
Factory
-
3-11-4
Max Output
Submenu for
specifying the
maximum output
values
-
-
-
-
-
-
3-11-4-1
Max Out Freq
Assignment of
maximum output
frequency
50
50
25
70
Hz
Customer
-
3-11-4-2
Max Out Current
Assignment of
maximum output
current
0
0
0
500
A
Customer
-
3-11-5
PD Settings
Submenu for
PumpDrive settings
-
-
-
-
-
-
-
3-11-5-1
PDrive Size
PumpDrive power
class
3
3
1
16
-
Customer
-
3-11-5-2
Offset DC-Link
Offset DC link
voltage
350
350
200
365
V
Factory
-
3-12
Adv Pump Ctrl
Menu for Advanced Pump Control
3-12-1
Flow Rate Meas
Submenu for flow
rate (Q)
measurement
3-12-1-1
Flow Rate Meas
Q measurement/
estimation
1
1
Customer Measured
P/Q calculated
3-12-2
Low Q Limit
Submenu for
minimum flow rate
Q
3-12-2-1
Start Learn Prf
Start learning
function: Learn load
profile across
frequency range
1
1
Customer OFF
Start
3-12-2-2
P % @ 30% fmax
Learning function:
Measured load P1 at
30 % of fmax
0
0
0
110
kW
Customer
3-12-2-3
P % @ 40% fmax
Learning function:
Measured load P2 at
40 % of fmax
0
0
0
110
kW
Customer
3-12-2-4
P % @ 50% fmax
Learning function:
Measured load P3 at
50 % of fmax
0
0
0
110
kW
Customer
10 Parameter lists
124 of 162