Parameter Description
Factory
setting
Setting
Unit
Access level
Possible settings
EP
MP
Min.
Max.
3-12-3-23
P_2
Data point H/P/Q
curve P_2 at
nominal speed
0
0
0
999
kW
Customer
3-12-3-24
P_3
Data point H/P/Q
curve P_3 at
nominal speed
0
0
0
999
kW
Customer
3-12-3-25
P_4
Data point H/P/Q
curve P_4 at
nominal speed
0
0
0
999
kW
Customer
3-12-3-26
P_5
Data point H/P/Q
curve P_5 at
nominal speed
0
0
0
999
kW
Customer
3-12-3-27
P_6
Data point H/P/Q
curve P_6 at
nominal speed
0
0
0
999
kW
Customer
3-12-4
Pump Protection
Submenu
3-12-4-1
Q Lim High Flow
Maximum
permissible value for
Q
100
100
0
150
%
Customer
3-12-4-2
Q Hi Timeout Tm
Time delay for
overload detection
20
20
0
120
s
Customer
3-12-4-3
Q Hi Timeout Fn
Perform function
when overload
occurs
1
1
Customer No Function
Warning
Stop & Trip
3-12-4-4
Q Lim Low Flow
Limit value for
minimum flow stop
for Q
100
100
0
150
%
Customer
3-12-4-5
Q Lo Timeout Tm
Time delay for low
flow detection
20
20
0
120
s
Customer
3-12-4-6
Q Lo Timeout Fn
Perform function
when low flow
occurs
1
1
Customer No Function
Warning
Stop & Trip
3-12-4-7
Hyd Blk Factor
Limit value for
impeller blockage
85
85
0
100
%
Customer
3-12-4-8
Hyd Blck Tmout
Time delay for
impeller blockage
10
10
0
1000
s
Customer
3-12-4-9
Dry Run Factor
Limit value for dry
running
70
70
0
100
%
Customer
3-12-4-10
Dry Run Timeout
Time delay for dry
running
5
5
0
1000
s
Customer
3-12-4-11
Dry Run Enable
Enable/disable dry
running function
2
2
Customer Disabled
Enabled
3-12-5
Multipump Conf
Submenu
10 Parameter lists
PumpDrive
127 of 162