Parameter Description
Factory
setting
Setting
Unit
Access level
Possible settings
EP
MP
Min.
Max.
3-6-3-5
An IN 2 Low
Selection of lower
limit value for
analog input
monitoring
0
0
3-8-3-7 3-8-3-8 3-8-3-6
Customer
-
3-6-3-6
An IN 2 High
Selection of upper
limit value for
analog input
monitoring
100
100
3-8-3-7 3-8-3-8
3-8-3-6
Customer
-
3-6-3-7
An IN2 Wrn TDly
Time delay for
function
5
5
0
60
s
Customer
-
3-6-3-8
An IN 2 Wrn Fnc
Analog input
monitoring function
1
1
-
-
Customer No Function
Warning
Stop & Trip
3-6-4
Load Warnings
Submenu for
displaying load-
dependent warnings
-
-
-
-
-
-
-
3-6-4-1
Hi Ld @ Lo Mo F
Selection of
overload at low
motor frequency
60
60
0
3-6-4-2
%
Customer
-
3-6-4-2
Hi Ld @ Hi Mo F
Selection of
overload at high
motor frequency
90
90
3-6-4-1
100
%
Customer
-
3-6-4-3
Hi Load Profile
Selection of
overload profile
1
1
-
-
-
Customer Linear
Square
Cubic
3-6-4-4
Hi Load Tm Dly
Selection of
overload time delay
5
5
0
30
s
Customer
-
3-6-4-5
High Load Fnc
Selection of
overload functions
1
5
-
-
-
Customer No Function
Warning
Stop & Trip
3-6-4-6
Lo Ld @ Lo Mo F
Selection of low
load at low motor
frequency
30
30
0
3-6-4-7
%
Customer
-
3-6-4-7
Lo Ld @ Hi Mo F
Selection of low
load at high motor
frequency
60
60
3-6-4-6
100
%
Customer
-
3-6-4-8
Lo Load Profile
Selection of low
load profile
1
1
-
-
-
Customer Linear
Square
Cubic
3-6-4-9
Lo Load Tm Dly
Selection of low
load time delay
10
10
0
30
s
Customer
-
3-6-4-10
Low Load Fnc
Selection of low
load functions
1
2
-
-
-
Customer No Function
Warning
Stop & Trip
3-6-5
Setpoint Warns
Submenu for
setpoint monitoring
-
-
-
-
-
-
-
3-6-5-1
Min Setpoint
Selection of low
limit value for
setpoint monitoring
0
0
0
3-5-1-3
3-2-2-1
Customer
-
10 Parameter lists
118 of 162
PumpDrive