Parameter Description
Factory
setting
Setting
Unit
Access level
Possible settings
EP
MP
Min.
Max.
3-12-2-5
P % @ 60% fmax
Learning function:
Measured load P4 at
60 % of fmax
0
0
0
110
kW
Customer
3-12-2-6
P % @ 70% fmax
Learning function:
Measured load P5 at
70 % of fmax
0
0
0
110
kW
Customer
3-12-2-7
P % @ 80% fmax
Learning function:
Measured load P6 at
80 % of fmax
0
0
0
110
kW
Customer
3-12-2-8
P % @ 90% fmax
Learning function:
Measured load P7 at
90 % of fmax
0
0
0
110
kW
Customer
3-12-2-9
P % @ 100% fmax
Learning function:
Measured load at
100 % of fmax
0
0
0
110
kW
Customer
3-12-2-10
learning time
Measurement
period for each
measuring point
30
30
30
500
s
Customer
3-12-2-11
learn meas fail
Permissible
measuring error, in
percent, outside a
predefined
tolerance band
5
5
2
20
%
Customer
3-12-3
Q/P/H Curves
Submenu for
displaying H/P/Q
curves
3-12-3-1
Rated p speed
Specification of
nominal pump
speed
0
0
0
9999
rpm
Customer
3-12-3-2
RhoRho
Specification of
density of fluid
1000
1000
0
9999
kg/m3
Customer
3-12-3-3
No of Stages
Specification of
number of stages
1
1
0
100
Customer
3-12-3-4
Qopt
Specification of flow
rate at best
efficiency point
0
0
0
9999
m3/h
Customer
3-12-3-5
Qmin
Specification of
minimum flow rate
0
0
0
9999
m3/h
Customer
3-12-3-6
Qmax
Specification of
maximum flow rate
0
0
0
9999
m3/h
Customer
3-12-3-7
Q_0
Data point H/P/Q
curve Q_0 at
nominal speed
0
0
0
9999
m3/h
Customer
10 Parameter lists