Parameter Description
Possible settings
Factory setting
3-6-3-3
Analog input 1 time
delay
0..60 (s)
Access: Standard
5 s
3-6-3-4
Function
Analog input 1 –
Monitoring
1 - No Function
2 - Warning
3 - Stop and Trip
1 - No Function
3-6-3-5
Lower limit
Analog input 2
Analog IN 2 Low
(3-8-3-7)
to Analog IN
2 High
(3-8-3-8)
in Analog IN 2 Unit
(3-8-3-6)
0
3-6-3-6
Upper limit for analog
input 2
100
3-6-3-7
Analog input 2 time
delay
0..60 (s)
Access: Standard
5 s
3-6-3-8
Function
Analog input 2 –
Monitoring
1 - No Function
2 - Warning
3 - Stop and Trip
1 - No Function
3-8-2-6
Unit of Analog IN 1
1
3-8-2-7
Low value for Analog
IN 1
0 to Analog IN 1 High
(3-8-2-8)
in
Analog IN 1 Unit
(3-8-2-6)
0
3-8-2-8
High value for Analog
IN 1
Analog IN 1 Low
(3-8-2-7)
to 9999 in
Analog IN 1 Unit
(3-8-2-6)
100
3-8-3-6
Unit of Analog IN 2
1
3-8-3-7
Low value for Analog
IN 2
0 to Analog IN 2 High
(3-8-3-8)
in
Analog IN 2 Unit
(3-8-3-6)
0
3-8-3-8
High value for Analog
IN 2
Analog IN 2 Low
(3-8-3-7)
to 9999 in
Analog IN 2 Unit
(3-8-3-6)
100
Table 84: Parameters for monitoring the setpoint and actual value
Parameter Description
Possible settings
Factory setting
3-6-5-1
Lower limit
Setpoint monitoring
0 to Maximum Setpoint
(3-5-1-3)
in
physical setpoint unit
(3-2-2-1)
0
3-6-5-2
Upper limit
Setpoint monitoring
Minimum Setpoint
(3-5-1-2)
to 100 in
physical setpoint unit
(3-2-2-1)
100
3-6-5-3
Time delay
Setpoint monitoring
0..60 (s)
5 s
3-6-5-4
Setpoint warning
function
1 - No Function
2 - Warning
3 - Stop and Trip
1 - No Function
3-6-6-1
Lower limit
Actual value
monitoring
0 to Feedback High Limit
(3-6-6-2)
in
physical setpoint unit
(3-2-2-1)
0
3-6-6-2
Upper limit
Actual value
monitoring
Feedback Low Limit
(3-6-6-1)
to 9999 in
physical setpoint unit
(3-2-2-1)
100
3-6-6-3
Time delay
Actual value
monitoring
0..60 (s)
5 s
3-6-6-4
Actual value
monitoring function
1 - No Function
2 - Warning
3 - Stop and Trip
1 - No Function
3-5-1-2
Lower limit
Setpoint monitoring
0 to Maximum Setpoint
(3-5-1-3)
in
physical setpoint unit
(3-2-2-1)
0
3-5-1-3
Upper limit
Setpoint monitoring
Minimum Setpoint
(3-5-1-2)
to 9999 in
physical setpoint unit
(3-2-2-1)
100
3-2-2-1
Physical unit of setpoint Selection list III (
129)
Access: Service
1
7 Commissioning/shutdown
84 of 162
PumpDrive