P7 terminal strip, terminals 1 to 4:
▪
The function of the two volt-free relays (NO) can be parameterised via the
control panel.
P7 terminal strip, terminals 5 to 10:
▪
Analog signals from a higher-level control station must be electrically isolated
when they are transmitted to PumpDrive, for example by using isolating
amplifiers.
▪
If an external voltage or current source is used for the analog inputs, the ground
of the setpoint or sensor sources is applied to terminal P7:10.
▪
The +24 V DC voltage source (terminals P7:5 and P7:7) is used as the power
supply for the actual value sensor if PumpDrive is in closed-loop control mode.
▪
Alternatively, analog input 2 can be connected to the mains/motor/PTC terminal
strip. In this case, do not assign the input on terminal strip P7:6.
5.4.3.7
Connecting the control panel
DANGER
Improper handling
Damage to PumpDrive!
▷
Only connect or remove the control panel when it is de-energised.
CAUTION
Electrostatic charging
Damage to the electronics!
▷
Before starting work on the control panel, personnel must ensure that they are
free of electrostatic charges.
▷
Only connect or remove the control panel when it is de-energised.
Mounting the standard control panel
✓
The following connections are available: 24 V, GND
1.
Undo the screws of the mounted blanking plate/control panel and remove the
blanking plate/control panel.
1
2
Fig. 18: Connecting cable ends
1
Mini USB connection
2
Supply voltage
2.
Connect the red line (24 V) to terminal strip P4 (terminal P4:13) of PumpDrive.
3.
Connect the black line (GND) to terminal strip P4 (terminal P4:20) of PumpDrive.
Relay outputs
Analog inputs
5 Installation at Site
34 of 162
PumpDrive