Original Operating Manual for KLARO Small Wastewater Treatment Plant V.15.07

6.1.1. Mode of Operation

The water level is measured by the pressure in the 
charging lifter during the charging phase. If the water 
level in the sludge storage/buffer (chamber 1) 
exceeds a preset fill level ("level measurement 
setting "), the system starts a treatment cycle. If the 
level is not reached, the system enters into cycle 
pause for 6 hours. During the pause, the SBR 
reactor is aerated only occasionally in order to keep 
the bacteria alive. After 4 consecutive measurements 
during which the preset water level in the first 
chamber is not reached, the plant will pump water 
back from the reactor into the first chamber via the 
excess sludge lifter (recirculation). This will create an 
artificial supply and the water level rises, which can 
cause a cycle start after the following 

measurements. The duration of the 
recirculation, and thus the delivered volume of 
water, can be adjusted in the service menu. As a result, the reactor is given a new supply after a certain 
time even in the event of little or no wastewater supply. The regular treatment line can therefore be 
maintained over a longer period even in the absence or underload of wastewater.
The number of treatment cycles performed can be queried via the menu item Operating Hours. The 
treatment cycles actually carried out are compared with the cycles running in automatic mode (4 per day) 
and displayed as a percentage (25% to 100% use of capacity). 

6.1.2. Commissioning

Fall Hazard

When working near the open cover of the septic tank, there is a hazard of tripping 
and falling!
The open tank must be secured by appropriate measures.

The first chamber (sludge storage/buffer), in which the charging lifter is located, must be filled with water 
up to the level at which a treatment cycle is to be triggered. For this purpose, a marking with the 
recommended fill level is attached to the charging lifter 

airlift

.blue.

1st step: Calibrating the pressure sensor,

The calibration of the sensor is essential for the commissioning of the underload detection. Please go 
through the following points carefully in order:

Service Code

Input

Go to the menu item "SERVICE CODE INPUT," press the 

key and enter 

the following code when prompted:  9 9 9 9

Calibrate?

No

Use the arrow keys (

← →

) to select "CALIBRATE YES" and confirm with the 

key and start the calibration...

Figure 11: Charging Lifter

Charging lifter

Minimum

water level

Water level

By activating 

treatment cycle

Chamber 2
SBR

Chamber 1
SS+ P

Air hose

red

KLARO GmbH

Original Operating Manual for KLARO Small Wastewater Treatment Plant V.15.07

25

Measurement in 

progress

3 measurement processes are performed automatically

Enter current

fill 

level: 000 cm

Enter the current level b of chamber 1, which you measured with a yardstick 

(measured from the tank bottom to the water surface) and confirm with 

.

Save?

____ cm    No 

The measure now specified is the distance 

c

from the tank bottom to the inlet

point of the lifter. Use the arrow keys (

← →

) to select "Save Yes" and confirm 

with the 

key. The calibration is now complete and you can exit this menu 

by pressing the "ESC" key.

2nd step: Setting the Control Parameters

Setting the control parameters for the level measurement is essential for proper functioning of the plant. 
Please go through the following points carefully in order:

Service Code

Input

Go to the menu item "SERVICE CODE INPUT," press the 

key and enter 

the general service code when prompted.

Level Measurement

Setting

Use the left arrow (

) key to select "Level Measurement Setting" and confirm 

with the 

key.

Level

Start from:   000 cm

Enter the water level 

b

, at which a treatment cycle is to be started. Confirm 

with the 

key.

Recirculation

2 min

Use the numeric keys to enter the value "2 min" and confirm with the 
key. For plants that are very underutilised, we recommend entering a higher 
value. The required settings are now complete and you can exit the menu by 
pressing "ESC".

Warning Backwater
From:           000 cm

(from Software 8.29)

NOTE: 

Enabling the backwater alarm is not mandatory for the correct 

functioning of the plant. By saving the value 000 cm, this warning is disabled.

To enable, measure the height between the bottom of the tank and lower edge of the emergency 
overflow in the partition or, for full cycle plants, at the drain.

3rd step: Functional check

The level measurement can now be performed in manual mode for testing purposes. To do so, the level 
measurement must be switched on with number "1." The controller then automatically performs a 
measurement. After the operation, the measured value appears.

6.1.3. Switching Off the Level Measurement

To turn off the level measurement and allow timed cycles to run again, the 2nd steps described above 
must be repeated. The water level b must be set to 0 cm. Recirculation can remain set to 2 minutes. 

6.1.4. Safety and Fault Messages

If the sensor measures a value below 40 mbar, the following message is displayed: "Malfunction: min. 
level.“ In this event, the plant switches to normal timed operation. The reason for this fault is either a 
water level that is too low (

≤ 40 cm) in the sludge storage/buffer or a leak in the pressure or measuring 

line. We recommend to contact the manufacturer in this case.

KLARO GmbH

2

Original Operating Manual for KLARO Small Wastewater Treatment Plant V.15.07

IMPORTANT: 

This Operating Manual contains information about the plant, from installation 

to maintenance, and must therefore be read before commissioning of the 

plant!

All safety instructions must be observed!

The Operating Manual must be kept readily available during the operation of 

the plant!

Plant Specifications

For any questions in the course of the operation of the plant, the specifications of your plant should 
be noted as follows. With the help of this information, our staff will be able to help you more quickly 
in the event of a malfunction. The specifications can be found on the nameplate, which is located 
on the outside of the cabinet door for indoor cabinets, and inside the cabinet for outdoor cabinets.

Small Wastewater Treatment 

Plant

PT

Sludge storage

Buffer

SB-Reactor

Approval No.:

Process class:

Certified:

Cabinet:

Controller:

Compressor: 

Denomination:

Serial No.:

Article No.:

Additional module:

Article No.:

El. Connected load:

KLARO GmbH

2

Original Operating Manual for KLARO Small Wastewater Treatment Plant V.15.07

IMPORTANT: 

This Operating Manual contains information about the plant, from installation 

to maintenance, and must therefore be read before commissioning of the 

plant!

All safety instructions must be observed!

The Operating Manual must be kept readily available during the operation of 

the plant!

Plant Specifications

For any questions in the course of the operation of the plant, the specifications of your plant should 
be noted as follows. With the help of this information, our staff will be able to help you more quickly 
in the event of a malfunction. The specifications can be found on the nameplate, which is located 
on the outside of the cabinet door for indoor cabinets, and inside the cabinet for outdoor cabinets.

Small Wastewater Treatment 

Plant

PT

Sludge storage

Buffer

SB-Reactor

Approval No.:

Process class:

Certified:

Cabinet:

Controller:

Compressor: 

Denomination:

Serial No.:

Article No.:

Additional module:

Article No.:

El. Connected load:

24

Summary of Contents for LA-100

Page 1: ...ro d u c t s M ade in Germ a n y Operating manual for KLARO small wastewater treatment plants We provide clean water No mechanical parts in the wastewater No pumps in the wastewater No electrical part...

Page 2: ...questions in the course of the operation of the plant the specifications of your plant should be noted as follows With the help of this information our staff will be able to help you more quickly in t...

Page 3: ...ontroller 18 5 3 1 Querying Operating Hours 18 5 3 2 Manual Control of the Valves and the Cabinet Fan in Manual Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Qu...

Page 4: ...RO GmbH 2 Original Operating Manual for KLARO Small Wastewater Treatment Plant V 15 07 IMPORTANT This Operating Manual contains information about the plant from installation to maintenance and must th...

Page 5: ...6 1 1 Mode of Operation 24 6 1 2 Commissioning 24 6 1 3 Switching Off the Level Measurement 25 6 1 4 Safety and Fault Messages 25 6 2 Optional Functions 26 6 2 1 Connection of an external alarm devic...

Page 6: ...MoAnl 19 Factory Calibration Controller MoAnl 20 Submersible Pump for Additional Buffer Date of print 06 2015 KLARO GmbH 2 Original Operating Manual for KLARO Small Wastewater Treatment Plant V 15 07...

Page 7: ...rs KLplus KL24plus and KLbasic KL24base 23 6 1 Underload detection KLplus KL24plus 23 6 1 1 Mode of Operation 24 6 1 2 Commissioning 24 6 1 3 Switching Off the Level Measurement 25 6 1 4 Safety and Fa...

Page 8: ...s be left running except for maintenance purposes because proper wastewater treatment cannot be ensured otherwise KLARO GmbH 2 Original Operating Manual for KLARO Small Wastewater Treatment Plant V 15...

Page 9: ...al Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21 5 3 6 Display Settings 21 5 3 7 Service Menu and Action Code 21 5 4 Changing the Fuse...

Page 10: ...system essentially consists of 2 stages A sludge storage with integrated pre buffer and an activated sludge stage in a closed sequencing batch reactor SBR The upstream sludge storage with integrated b...

Page 11: ...oliday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21 5 3 6 Display Settings 21 5 3 7 Service Menu and Action Code 21 5 4 Changing the Fuses 22 5 5 Operation of Power Failure Detector 22 6...

Page 12: ...o holiday mode The holiday mode is a greatly reduced operating mode of the plant during longer periods without wastewater inflow Figure 1 Membrane Tube Diffusor Figure 2 Membrane Plate Diffusor KLARO...

Page 13: ...07 3 CONTENTS Page 1 About this Operating Manual 6 1 1 Original Language of Documentation 6 1 2 Completeness 6 1 3 Liability 7 2 Safety 7 2 1 Explanation of Warnings and Prohibitions 7 2 2 Hazard stat...

Page 14: ...tion about the plant from installation to maintenance and must therefore be read before commissioning of the plant All safety instructions must be observed The Operating Manual must be kept readily av...

Page 15: ...6 1 1 Mode of Operation 24 6 1 2 Commissioning 24 6 1 3 Switching Off the Level Measurement 25 6 1 4 Safety and Fault Messages 25 6 2 Optional Functions 26 6 2 1 Connection of an external alarm devic...

Page 16: ...riginal Operating Manual for KLARO Small Wastewater Treatment Plant V 15 07 IMPORTANT This Operating Manual contains information about the plant from installation to maintenance and must therefore be...

Page 17: ...22 6 Additional functions of the Controllers KLplus KL24plus and KLbasic KL24base 23 6 1 Underload detection KLplus KL24plus 23 6 1 1 Mode of Operation 24 6 1 2 Commissioning 24 6 1 3 Switching Off t...

Page 18: ...be read before commissioning of the plant All safety instructions must be observed The Operating Manual must be kept readily available during the operation of the plant Plant Specifications For any q...

Page 19: ...e Valves and the Cabinet Fan in Manual Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21 5 3 6 Display Settings 21 5 3 7 Service Menu and...

Page 20: ...19 12 2015 Mo 20 15 56 20 15 Mo 19 12 15 KLARO GmbH 2 Original Operating Manual for KLARO Small Wastewater Treatment Plant V 15 07 IMPORTANT This Operating Manual contains information about the plant...

Page 21: ...e KL controls 230V option for solenoid valves 16 5 2 Connections to the KL24 controller 24V option for stepper motor valves 16 5 3 Operating the Controller 18 5 3 1 Querying Operating Hours 18 5 3 2 M...

Page 22: ...rogram settings etc is saved However if no time and date is set no weekly operating hours of the units will be saved Future fault messages will be saved with an incorrect date KLARO GmbH 2 Original Op...

Page 23: ...astewater Treatment Plant 13 5 1 Connections to the KL controls 230V option for solenoid valves 16 5 2 Connections to the KL24 controller 24V option for stepper motor valves 16 5 3 Operating the Contr...

Page 24: ...ICE CODE INPUT press the key and enter the following code when prompted 9 9 9 9 Calibrate No Use the arrow keys to select CALIBRATE YES and confirm with the key and start the calibration Figure 11 Cha...

Page 25: ...Process Classes N and D 13 4 3 Systems with Additional Phosphate Elimination Process Class P 13 4 4 Systems with Additional Sanitation Process Class S 13 5 Control of the Small Wastewater Treatment Pl...

Page 26: ...chloride and ethylene oxide there is a hazard of explosion Consult the appropriate Material Safety Data Sheet before using phosphate precipitants Wear protective clothing when handling poly aluminium...

Page 27: ...he KL24 controller 24V option for stepper motor valves 16 5 3 Operating the Controller 18 5 3 1 Querying Operating Hours 18 5 3 2 Manual Control of the Valves and the Cabinet Fan in Manual Mode 19 5 3...

Page 28: ...o that the sludge storage space is sufficient for permanent full load operation and compliance with the operating and maintenance requirements for at least 12 months At a lower load this period is ext...

Page 29: ...gs and Prohibitions 7 2 2 Hazard statements 8 2 3 Warnings 9 2 4 Exclusion for Use 10 3 Warranty 10 4 Function of the SBR Plant 10 4 1 Plants for carbon elimination process classes C 11 4 2 Systems wi...

Page 30: ...o the workers in sewers and treatment plant Garbage bin Pipe cleaners Corrode pipes and seals poison the District collection centres KLARO GmbH 2 Original Operating Manual for KLARO Small Wastewater T...

Page 31: ...Manual Control of the Valves and the Cabinet Fan in Manual Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21 5 3 6 Display Settings 21 5 3...

Page 32: ...on of the cabinet fan Check air filter in the cabinet Shade location Provide cool ventilation Check air filter in the air compressor Check air compressor in manual mode Have maintenance company check...

Page 33: ...Wastewater Treatment Plant 13 5 1 Connections to the KL controls 230V option for solenoid valves 16 5 2 Connections to the KL24 controller 24V option for stepper motor valves 16 5 3 Operating the Con...

Page 34: ...anual contains information about the plant from installation to maintenance and must therefore be read before commissioning of the plant All safety instructions must be observed The Operating Manual m...

Page 35: ...2 Operating Instructions 29 8 Fault Messages and Troubleshooting 31 8 1 Fault Message on the Display 32 8 2 Unusual Water Levels Troubleshooting 33 KLARO GmbH Original Operating Manual for KLARO Smal...

Page 36: ...astewater Treatment Plant PT Sludge storage Buffer SB Reactor Approval No Process class Certified Cabinet Controller Compressor Denomination Serial No Article No Additional module Article No El Connec...

Page 37: ...epair and Operation 28 7 1 Sludge Evacuation 28 7 2 Operating Instructions 29 8 Fault Messages and Troubleshooting 31 8 1 Fault Message on the Display 32 8 2 Unusual Water Levels Troubleshooting 33 KL...

Page 38: ...eatment Plant PT Sludge storage Buffer SB Reactor Approval No Process class Certified Cabinet Controller Compressor Denomination Serial No Article No Additional module Article No El Connected load KLA...

Page 39: ...ntenance Repair and Operation 28 7 1 Sludge Evacuation 28 7 2 Operating Instructions 29 8 Fault Messages and Troubleshooting 31 8 1 Fault Message on the Display 32 8 2 Unusual Water Levels Troubleshoo...

Page 40: ...fer SB Reactor Approval No Process class Certified Cabinet Controller Compressor Denomination Serial No Article No Additional module Article No El Connected load KLARO GmbH 2 Original Operating Manual...

Page 41: ...ce Repair and Operation 28 7 1 Sludge Evacuation 28 7 2 Operating Instructions 29 8 Fault Messages and Troubleshooting 31 8 1 Fault Message on the Display 32 8 2 Unusual Water Levels Troubleshooting 3...

Page 42: ...Treatment Plant PT Sludge storage Buffer SB Reactor Approval No Process class Certified Cabinet Controller Compressor Denomination Serial No Article No Additional module Article No El Connected load...

Page 43: ...Repair and Operation 28 7 1 Sludge Evacuation 28 7 2 Operating Instructions 29 8 Fault Messages and Troubleshooting 31 8 1 Fault Message on the Display 32 8 2 Unusual Water Levels Troubleshooting 33 K...

Page 44: ...Wastewater Treatment Plant PT Sludge storage Buffer SB Reactor Approval No Process class Certified Cabinet Controller Compressor Denomination Serial No Article No Additional module Article No El Conne...

Page 45: ...l of the Valves and the Cabinet Fan in Manual Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21 5 3 6 Display Settings 21 5 3 7 Service Me...

Page 46: ...quickly in the event of a malfunction The specifications can be found on the nameplate which is located on the outside of the cabinet door for indoor cabinets and inside the cabinet for outdoor cabin...

Page 47: ...of the Valves and the Cabinet Fan in Manual Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21 5 3 6 Display Settings 21 5 3 7 Service Men...

Page 48: ...u more quickly in the event of a malfunction The specifications can be found on the nameplate which is located on the outside of the cabinet door for indoor cabinets and inside the cabinet for outdoor...

Page 49: ...s KL24plus and KLbasic KL24base 23 6 1 Underload detection KLplus KL24plus 23 6 1 1 Mode of Operation 24 6 1 2 Commissioning 24 6 1 3 Switching Off the Level Measurement 25 6 1 4 Safety and Fault Mess...

Page 50: ...quickly in the event of a malfunction The specifications can be found on the nameplate which is located on the outside of the cabinet door for indoor cabinets and inside the cabinet for outdoor cabin...

Page 51: ...ility 7 2 Safety 7 2 1 Explanation of Warnings and Prohibitions 7 2 2 Hazard statements 8 2 3 Warnings 9 2 4 Exclusion for Use 10 3 Warranty 10 4 Function of the SBR Plant 10 4 1 Plants for carbon eli...

Page 52: ...el besch digt ist muss es durch den Hersteller seine autorisierten H ndler oder qualifizierte Personen ersetzt werden um eine Gefahr zu vermeiden 6 Stellen Sie keine Gegenst nde auf das elektrische Ka...

Page 53: ...Setzen Sie Dichtung A11 in den Geh usedeckel und Dichtung B12 am Pumpengeh use ein dann befestigen Sie das Vordergeh use 10 mit den Sechskantschrauben 9 Ziehen Sie die Sechskantschrauben 9 nach und n...

Page 54: ...g B 1 2 3 13 Kolben 1 2 3 18 Federteller 1 2 3 19 Feder 1 2 3 7 Kolbenk rper Feder Federteller Fett Teflonschicht KLARO GmbH 2 Original Operating Manual for KLARO Small Wastewater Treatment Plant V 15...

Page 55: ...1 About this Operating Manual 6 1 1 Original Language of Documentation 6 1 2 Completeness 6 1 3 Liability 7 2 Safety 7 2 1 Explanation of Warnings and Prohibitions 7 2 2 Hazard statements 8 2 3 Warnin...

Page 56: ...ater Treatment Plant V 15 07 IMPORTANT This Operating Manual contains information about the plant from installation to maintenance and must therefore be read before commissioning of the plant All safe...

Page 57: ...4 4 Systems with Additional Sanitation Process Class S 13 5 Control of the Small Wastewater Treatment Plant 13 5 1 Connections to the KL controls 230V option for solenoid valves 16 5 2 Connections to...

Page 58: ...nt All safety instructions must be observed The Operating Manual must be kept readily available during the operation of the plant Plant Specifications For any questions in the course of the operation...

Page 59: ...3 7 Service Menu and Action Code 21 5 4 Changing the Fuses 22 5 5 Operation of Power Failure Detector 22 6 Additional functions of the Controllers KLplus KL24plus and KLbasic KL24base 23 6 1 Underload...

Page 60: ...ant All safety instructions must be observed The Operating Manual must be kept readily available during the operation of the plant Plant Specifications For any questions in the course of the operation...

Page 61: ...4 Changing the Fuses 22 5 5 Operation of Power Failure Detector 22 6 Additional functions of the Controllers KLplus KL24plus and KLbasic KL24base 23 6 1 Underload detection KLplus KL24plus 23 6 1 1 Mo...

Page 62: ...he plant All safety instructions must be observed The Operating Manual must be kept readily available during the operation of the plant Plant Specifications For any questions in the course of the oper...

Page 63: ...1 5 3 7 Service Menu and Action Code 21 5 4 Changing the Fuses 22 5 5 Operation of Power Failure Detector 22 6 Additional functions of the Controllers KLplus KL24plus and KLbasic KL24base 23 6 1 Under...

Page 64: ...ily available during the operation of the plant Plant Specifications For any questions in the course of the operation of the plant the specifications of your plant should be noted as follows With the...

Page 65: ...5 5 Operation of Power Failure Detector 22 6 Additional functions of the Controllers KLplus KL24plus and KLbasic KL24base 23 6 1 Underload detection KLplus KL24plus 23 6 1 1 Mode of Operation 24 6 1 2...

Page 66: ...the specifications of your plant should be noted as follows With the help of this information our staff will be able to help you more quickly in the event of a malfunction The specifications can be fo...

Page 67: ...ying Operating Hours 18 5 3 2 Manual Control of the Valves and the Cabinet Fan in Manual Mode 19 5 3 3 Setting Date Time 20 5 3 4 Set Holiday Mode 20 5 3 5 Query Malfunctions Query Old Malfunctions 21...

Page 68: ...0615 part of the GRAF group KLARO GmbH Spitzwegstra e 63 95447 Bayreuth Telephone 49 0 921 16279 0 Fax 49 0 921 16279 100 E Mail info klaro eu More information at www klaro eu Technical hotline 49 0...

Reviews: