Chapter 7. Service
7-7
CAUTION
Manually activating setpoint relays
may cause damage if control equip-
ment is connected. Disconnect control
equipment before proceeding.
A typical setpoint test display looks like this:
• SP 02
is the current setpoint reference
number (referred to as SP2 when you
added it in the
I/O
Menu).
• SL 02
is the slot number of the setpoint
PCB.
• Ch2
is the channel number of the setpoint
on the setpoint PCB. Each setpoint PCB
has eight individual channels.
• On
indicates the current On/Off status of
the setpoint. Pressing the F1, F2, or F3
Key toggles the setpoint between
On
and
Off.
Pressing the Up and Down Arrow Keys or the
Enter Key toggles the display between the
setpoints for the current vessel.
Pressing the Esc Key or Auto/Man Key
terminates the test. Once the test is
terminated, the setpoints return to
automatic control.
4/20
This menu allows you to calibrate the 0/4 and
20 mA outputs to the device that is receiving
the current output. It also allows you to set
the current output to specific values for test
purposes. The
4/20
Menu has two submenus:
Iadj
This menu is used to manually assign
counts-to-milliamps outputs for 0 mA, 4 mA,
and 20 mA outputs to calibrate to another
device. Follow this procedure:
1. Put the Weigh II in the Manual Mode, go to
the
Main
Menu, the
Service
Menu, the
4/20
Menu, and then the
Iadj
Menu. The
display shows:
2.
Next
(F1) scrolls the display forward
through all the current channels.
Back
(F2)
scrolls the display backward through all
the current channels. Scroll to the desired
current channel using the F1 or F2 Key.
3. Press the F3 Key to access
Select
. The
display shows:
Note
If you have set up 4-20 mA output, the
Weigh II ignores anything you enter for
0 mA. Similarly, if you have set up 0-
20 mA output, the Weigh II ignores
anything you enter for 4 mA.
4. Press a Function Key (F1, F2, or F3) to
assign counts to the associated current
output. If you select F1 (0 mA), the display
looks like this:
5. Use the keypad or the Up and Down Arrow
Keys to change the counts if desired.
Press the Enter Key to save the value in
memory. The display flashes a message
acknowledging your selection and returns
to:
6. If desired, repeat Steps 4 and 5 for the
other current output, and repeat Steps 2
through 5 for other current channels.
Test
This function allows manual activation of
current output channels outside of normal
control. The system issues a warning that the
automatic control of current outputs assigned
to the currently selected channel is trans-
ferred to manual control, and requests
verification that that is what you want to do.
CAUTION
Manually activating current output can
cause damage if control equipment is
connected. Disconnect control equip-
ment before proceeding.
SP 02 :SL 02:Ch2
TOGGLE STATE>ON
F1 F2 F3
CURRENT CHAN#: 1
Next Back Select
F1 F2 F3
SELECT CAL POINT
0mA 4mA 20mA
F1 F2 F3
0mA CAL POINT
> X cnt
F1 F2 F3
SELECT CAL POINT
0mA 4mA 20mA
F1 F2 F3
Summary of Contents for Weigh II
Page 12: ...2 4 Chapter 2 Hardware Installation...
Page 20: ...3 8 Chapter 3 Menu Tree Keyboard Functions and Quick Start...
Page 50: ...6 12 Chapter 6 Calibration...
Page 68: ...A 2 Appendix A Product Specifications...
Page 70: ...B 2 Appendix B Summary of Commands Used When Vessel Mounting Hot Keys...
Page 77: ...Appendix E E 1 This appendix not used at this time...
Page 78: ...Appendix E E 2...
Page 80: ...Appendix F Technical Drawings F 2...
Page 81: ...Appendix F Technical Drawings F 3...
Page 82: ...Appendix F Technical Drawings F 4...
Page 83: ...Appendix F Technical Drawings F 5...
Page 84: ...Appendix F Technical Drawings F 6...
Page 85: ...Appendix F Technical Drawings F 7...
Page 86: ...Appendix F Technical Drawings F 8...
Page 87: ...Appendix F Technical Drawings F 9...
Page 88: ...Appendix F Technical Drawings F 10...
Page 89: ...Appendix F Technical Drawings F 11...
Page 90: ...Appendix F Technical Drawings F 12...
Page 91: ...Appendix F Technical Drawings F 13...
Page 92: ...Appendix F Technical Drawings F 14...
Page 93: ...Appendix F Technical Drawings F 15...
Page 94: ...Appendix F Technical Drawings F 16...
Page 95: ...Appendix F Technical Drawings F 17...
Page 96: ...Appendix F Technical Drawings F 18...
Page 97: ...Appendix F Technical Drawings F 19...
Page 98: ...Appendix F Technical Drawings F 20...
Page 99: ...Appendix F Technical Drawings F 21...
Page 100: ...Appendix F Technical Drawings F 22...
Page 101: ...Appendix F Technical Drawings F 23...
Page 102: ...Appendix F Technical Drawings F 24...
Page 103: ...Appendix F Technical Drawings F 25...
Page 104: ...Appendix F Technical Drawings F 26...
Page 105: ...Appendix F Technical Drawings F 27...
Page 106: ...Appendix F Technical Drawings F 28...
Page 107: ...Appendix F Technical Drawings F 29...
Page 108: ...Appendix F Technical Drawings F 30...
Page 109: ...Appendix F Technical Drawings F 31...
Page 110: ...Appendix F Technical Drawings F 32...
Page 116: ...Appendix G Calculation of Maunal Calibration Parameters G 6...