Starting master-slave-control parallel operation
CAUTION
•
To start master-slave-control parallel operation, always follow the
procedure below.
If the POWER switch of the master unit is turned ON before those
of the slave units, the master also outputs a portion of the current
output through the slaves, disabling constant voltage operations.
1.
Check that all POWER switches of the master and slave units are OFF.
2.
Turn on the POWER switch of each slave unit.
"C.C" lights up on the control panel of each slave unit, indicating that the unit is
in constant current operation mode. Because no signal is issued from the master
unit, the master remains in standby status.
3.
Turn on the POWER switch of the master unit.
"C.V" lights up on the master unit control panel, indicating that the unit is in
constant voltage operation mode.
4.
The same output voltage and current indicated on the master unit are
also displayed on all the slave units.
This means that the total current of all the units is applied to the load.
Finishing the master-slave-control parallel operation
CAUTION
•
To finish master-slave-control parallel operation, always observe
the following procedure.
If the POWER switches of the slave units is turned ON before
those of the master unit, the master also outputs a portion of the
current output through the slaves, disabling constant voltage
operations.
1.
Turn off the POWER switch of the master unit.
2.
Turn off the POWER switch of each slave unit.