Table 3-1
Nominal Cross-sectional Areas of Cables and
Allowable Currents
Nominal cross-
sectional area
[mm
2
]
AWG
(Reference
cross-sectional
area)
[mm
2
]
Allowable
current (*)
[A]
(Ta = 30℃)
Current
recommended
by Kikusui
[A]
2
14
(2.08)
27
10
3.5
12
(3.31)
37
-
5.5
10
(5.26)
49
20
8
8
(8.37)
61
30
14
5
(13.3)
88
50
22
3
(21.15)
115
80
30
2
(33.62)
139
-
38
1
(42.41)
162
100
50
1/0
(53.49)
190
-
60
2/0
(67.43)
217
-
80
3/0
(85.01)
257
200
100
4/0
(107.2)
298
-
125
-
-
344
-
150
-
-
395
300
200
-
-
469
-
*: Excerpts from Japanese laws related electrical equipment
Withstand voltage of load cables
For load cables, use cable with a higher voltage rating than the isolation voltage of
the unit. For more information, see 2.6 "Grounding the output terminal".