271
16.30.3.21
Wiring for cable connections using
Wago System 750 Series Controllers
with D-Sub 9 Female
Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 9 Male Socket Cable)
HMI PLC[RS-485]
Connect to Wago System 750 Series Controllers
with RS485 Port
1 RXD-
Æ
8 TXD-
2 RXD+
Æ
3 TXD+
3 TXD-
Æ
7 RXD-
4 TXD+
Æ
2 RXD+
5 GND
Æ
5 GND
Shield
Æ
Earth Ground
16.30.3.22
Wiring for cable connections using
Watlow MLS300 Series CPU’s
with RS485 RJ-12 Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Socket to RJ-12 Female Plug Cable)
HMI PLC[RS-485]
Connect to Watlow MLS300 Series CPU
with RS422 Port
1 RXD-
Æ
5 TXD-
2 RXD+
Æ
2 TXD+
3 TXD-
Æ
4 RXD-
4 TXD+
Æ
6 RXD+
5 GND
Æ
3 GND
1
Æ
Shield
Æ
Earth Ground
16.30.3.23
Wiring for cable connections using
Watlow Anafaze PPC2000 Series Controllers
with RS485 RJ-
12 Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Socket to RJ-12 Female Plug Cable)
HMI PLC[RS-485]
Connect to Watlow MLS300 Series CPU
with RS422 Port
1 RXD-
Æ
4 TXD-
2 RXD+
Æ
3 TXD+
3 TXD-
Æ
5 RXD-
4 TXD+
Æ
2 RXD+
5 GND
Æ
1 GND
6
Æ
Shield
Æ
Earth Ground
16.30.3.24
Wiring for cable connections using
TSX Twido CPU’s
with RS485 Round 8 pin MiniDIN ports.
KEP Part#: (Not Available) (D-Sub 9 Female Socket to 8 pin MiniDIN Male Plug Cable)
Summary of Contents for MMI-1500