224
16.10.3.2
Wiring for cable connections using
GE 90
Series CMM Modules
with RS422 D-Sub 25 Female Plug
ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 25 Male Socket Cable)
HMI PLC[RS-485]
Connect to GE 90
Series CMM Modules with RS422 Port
1 RXD-
Æ
9 SD(A)
2 RXD+
Æ
21 SD(B)
3 TXD-
Æ
13 RD(A)
4 TXD+
Æ
25 RD(B)
5 GND
Æ
7 SG
10 RTS(A)
Æ
11 CTS(A)
22 RTS(B)
Æ
23 CTS(B)
Shield
Æ
Earth Ground
16.10.3.3
Wiring for cable connections using
GE 90
Series CMM Modules
with RS232 D-Sub 25 Female Plug
ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 25 Male Socket Cable)
HMI PLC[RS-232]
Connect to GE 90
Series CMM Modules with RS232 Port
2 TXD
Æ
3 RXD
3 RXD
Æ
2 TXD
5 GND
Æ
7 GND
4 RTS
Æ
5 CTS
8 DCD
Æ
20 DTR
1
Æ
Shield
Æ
Earth Ground
16.10.3.4 Wiring for cable connections using
GE 90/70
Series and 351, 352, 363 and 364 CPU’s
with RS232
RJ-12 socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to RJ-12 Male Plug Cable)
HMI PLC[RS-232]
Connect to GE 90/70
Series 351 & 352 CPU’s with RS232 Port
2 TXD
Æ
5 RXD
3 RXD
Æ
2 TXD
5 GND
Æ
3 GND
Shield
Æ
Earth Ground